5. Technical Data
5.1. Technical Data
Nomen-
cla-
ture
1)
Parameter
Protect PV
10 kW
Protect PV
12.5 kW
Protect PV
15 kW
AC
P
ac,r
Max./Nom. power AC
10000 W
12500 W
15000 W
Reactive power range
0-6.0 kVA
r
0-7.5 kVA
r
0-9.0 kVA
r
V
ac,r
AC voltage range (P-N)
3x230 V ± 20 %
3x230 V ± 20 %
3x230 V ± 20 %
Nominal current AC
3 x 15 A
3 x 19 A
3 x 22 A
I
acmax
Max. current AC
3 x 15 A
3 x 19 A
3 x 22 A
AC current distortion (THD
%)
< 5 %
< 5 %
< 5 %
cosphi
ac,r
Power factor at 100 % load 0.99
0.99
0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
0.8 over-excited
0.8 under-excited
0.8 over-excited
0.8 under-excited
“Connecting” power loss
10 W
10 W
10 W
Night-time power loss (off
grid)
< 5 W
< 5 W
< 5 W
f
r
Grid frequency
50 ± 5 Hz
50 ± 5 Hz
50 ± 5 Hz
DC
Nominal power DC
10300 W
12900 W
15500 W
Max. recommended PV
power at STC
2)
11800 Wp
14700 Wp
17700 Wp
V
dc,r
Nominal voltage DC
700 V
700 V
700 V
V
mppmin
-
V
mppmax
MPP voltage - nominal
power
3)
430-800 V
358-800 V
430-800 V
MPP efficiency
99.9 %
99.9 %
99.9 %
V
dcmax
Max. DC voltage
1000 V
1000 V
1000 V
V
dcstart
Turn on voltage DC
250 V
250 V
250 V
V
dcmin
Turn off voltage DC
250 V
250 V
250 V
I
dcmax
Max. current DC
2x12 A
3x12 A
3x12 A
Max. short circuit current
DC at STC
2x12 A
3x12 A
3x12 A
Min. on grid power
20 W
20 W
20 W
Efficiency
Max. efficiency
98 %
98 %
98 %
Euro efficiency, V at
dc,r
97.0 %
97.3 %
97.4 %
Other
Dimensions (L,W,H)
700x525x250 mm
700x525x250 mm
700x525x250 mm
Mounting recommendation Wall bracket
Wall bracket
Wall bracket
Weight
35 kg
35 kg
35 kg
Acoustic noise level
4
56 dB(A)
56 dB(A)
56 dB(A)
MPP trackers
2
3
3
Operation temperature
range
-25..60 °C
-25..60 °C
-25..60 °C
Nom. temperature range
-25..45 °C
-25..45 °C
-25..45 °C
Storage temperature
-25..60 °C
-25..60 °C
-25..60 °C
Overload operation
Change of operat-
ing point
Change of operat-
ing point
Change of operat-
ing point
Overvoltage category AC
Class III
Class III
Class III
Overvoltage category DC
Class II
Class II
Class II
PLA
Included
Included
Included
Reactive power
Protect PV and
Protect PV easy
Protect PV and
Protect PV easy
Protect PV and
Protect PV easy
Functional Safety
Islanding detection - loss of
mains
Three-phase moni-
toring (ROCOF)
Three-phase moni-
toring (ROCOF)
Three-phase moni-
toring (ROCOF)
Voltage magnitude
Included
Included
Included
Frequency
Included
Included
Included
DC content of AC current
Included
Included
Included
Insulation resistance
Included
Included
Included
RCMU - Type B
Included
Included
Included
Indirect contact protection
Yes (class I, groun-
ded)
Yes (class I, groun-
ded)
Yes (class I, groun-
ded)
Short circuit protection
Yes
Yes
Yes
Table 5.1: Specifications
5. Technical Data
8000038781_00_BAL_en / L00410564-01_02
23
5