16
(OPTIONAL ITEM) PDU
Dimensions
426x84.5x80 mm (WxHxD)
2.4kg
Electrical outputs
Output socket group 1
: 10A & 16A,
Programmable output
Output socket group 2
: 10A & 16A,
Normal output
Ratings
6000 VA / 6000 W
10000 VA / 10000 W
Output connection
Hardwired, output cable not
provided
(OPTIONAL ITEM) PDU, ENVIRONMENTAL AND SAFETY
Certifications
EN 62040-1
IEC/EN 62040-2: Cat. C2
IEC/EN 62040-3
EN 60950-1
EMC (Emissions)
(for output cable < 10m)
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
EMC (Immunity)
IEC 61000-2-2
IEC 61000-4-2, Level 4
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on
signal ports) IEC 61000-4-5, Level 4,
Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
Agency markings
CE
Operating temperature
0~40
℃
full load no derating
40~50
℃
output power derating to
50% load,
Charger current derating 50%
Storage temperature
-15 to 40°C (32 to 104°F) with
batteries
-25 to 60°C (5 to 140°F) without
batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above
sea level with 10% derating per
1000m