Description Adjustable
parameters
Presetting
Ambient
temperature
warning
[enabled], [disabled]
If enabled, UPS alarm when ambient
temperature >40 °C
enabled
REPO
operation
[normally open], [normally closed]
Normally open means UPS makes a
shutdown by a closing input state.
Normally closed means UPS makes a
shutdown by an opening input state.
Setting only available in UPS stand-
by mode.
normally closed
Reset
Cumulative
Consumption
kWh
[no], [yes]
If “no”, no action.
If “yes”, the Cumulative Consumption
kWh value is cleared and the date
and time stamp for this statistic is set
to the current date and time.
no
Battery
limit time
5h, 6h, ...14h, 15h, 16h, …999h,
disabled
Default “14h” means when work on
battery mode for more than 14 hours,
UPS will make bat low alarm and then
shutdown itself 30 minutes later even
battery voltage still above the
shutdown value.
Disabled means “No time limitation”
for battery mode.
14h
Auto reboot
[enabled], [disabled]
Enabled means UPS will auto restart
to normal mode while utility recover
after the UPS has been shutdown for
battery low.
enabled
Содержание Protect C.1000
Страница 1: ...BETRIEBSANLEITUNG OPERATING INSTRUCTIONS EN DE Protect C 1000 Protect C 2000 Protect C 3000 Protect C ...
Страница 2: ...2 ...
Страница 20: ...20 3 3 CE ZERTIFIKAT ...
Страница 24: ...24 5 2 RÜCKSEITIGE ANSICHT ANSCHLÜSSE Protect C 1000 Protect C 2000 Protect C 3000 ...
Страница 62: ...62 NOTIZEN ...
Страница 63: ...63 NOTIZEN ...
Страница 64: ...64 ...
Страница 82: ...82 3 3 CE CERTIFICATE ...
Страница 86: ...86 5 2 REAR VIEW CONNECTIONS Protect C 1000 Protect C 2000 Protect C 3000 ...
Страница 124: ...124 NOTES NOTES ...
Страница 125: ...125 NOTES ...
Страница 126: ...126 NOTES ...
Страница 127: ...127 ...