105
Description Adjustable
parameters
Presetting
External battery
modules
Configures the amount of
external battery units
<0>
Battery charged
% to restart
[0%], [10%], [20%], ...[100%]
On battery operation the UPS output
is turned off as soon as the battery
capacity is below the selected level.
0 %
Automatic
battery tests
[enabled], [disabled]
enabled
Periodic
battery test
[daily], [weekly], [monthly]
weekly
Automatic battery tests run according to “periodic battery test”, unless
disabled. During the test, the UPS transfers to Battery mode and
discharges the batteries approximately 10 seconds under the existing
load.
The “UPS on Battery” notice and the “Battery Low” alarm do not activate
during a battery test.
For automatic battery tests to run:
The “Automatic Battery Test” setting must be enabled.
The UPS must be in Normal mode, with no active alarms.
The battery system being tested must have sufficient reserve capacity.
With reference to the input voltage, the Bypass voltage window must
be within the range of tolerances.
Содержание Protect C.1000
Страница 1: ...BETRIEBSANLEITUNG OPERATING INSTRUCTIONS EN DE Protect C 1000 Protect C 2000 Protect C 3000 Protect C ...
Страница 2: ...2 ...
Страница 20: ...20 3 3 CE ZERTIFIKAT ...
Страница 24: ...24 5 2 RÜCKSEITIGE ANSICHT ANSCHLÜSSE Protect C 1000 Protect C 2000 Protect C 3000 ...
Страница 62: ...62 NOTIZEN ...
Страница 63: ...63 NOTIZEN ...
Страница 64: ...64 ...
Страница 82: ...82 3 3 CE CERTIFICATE ...
Страница 86: ...86 5 2 REAR VIEW CONNECTIONS Protect C 1000 Protect C 2000 Protect C 3000 ...
Страница 124: ...124 NOTES NOTES ...
Страница 125: ...125 NOTES ...
Страница 126: ...126 NOTES ...
Страница 127: ...127 ...