26
PD201806 AEG GRID-TIED SINGLE-PHASE SOLAR INVERTER V.1-18 EN
26
5.1 LED indicators
There are three LED indicators on the panel:
1.
“Run”, operation indicator, green;
2.
Warn” recoverable fault indicator, yellow;
3.
Fault”, unrecoverable fault indicator, red.
The inverter state includes 6 states of stand-by, self-inspection, power generation, recoverable fault and unrecoverable
fault; LED indicators are on, off and blinking. Please refer to table 5-1 for detailed state of inverter and LED indicators
state.
“ ”: LED indicator is off;
“ ” (green), “ ” (yellow), “ ” (red): LED indicator is blinking at every 0.25S or 0.5S;
“ (Green), “ ” (yellow), “ ” (red): LED indicator is on.
Inverter state
LED indicators
Description
Stand-by
All indicators are off:
No power on
Self-inspection
Green indicator blinks in every 0.25s, others off:
Power on and ready for self-inspection
Power generation
Green indicator is on, others off.
The inverter is running and grid-tied power is generated)
Green and yellow indicator are on, others are off:
(1) Grid-tied power generation, but clock fault (A007);
(2) Grid-tied power generation, but DC input fault (A001 or
E001);
(3) Grid-tied power generation, but fan fault (E006 or E012);
Recoverable fault
Yellow indicator blinks every 0.5s, others are off:
Inverter stand-by.
Public grid fault (A001, A003, A004, A005or A006);
Yellow indicator is on, others are off:
(1)
Inverter stand-by. Temperature abnormal(E006);
(2)
Inverter stand-by. DC input fault (E001);
Unrecoverable fault
Red indicator blinks every 0.5s, others are off: