Start and run the engine for at least 5 minutes to allow 
stabiliser to treat the entire fuel system.

OXYGENATED FUELS
DO NOT USE E10 or E85 FUEL. IT WILL VOID YOUR 
WARRANTY.
NOTE: 

Some conventional petrol are blended with alcohol or 

an ether compound. This type of petrol is collectively referred 
to as oxygenated fuel; in Australia known as Ethanol. The use 
of ethanol fuel, or fuels containing ethanol is not recommended 
for this product.

CAUTION: 

On a level surface with the engine off, check the oil level 
before each use of the generator. 

AC OPERATION

 

Ŷ

Unplug all loads from the generator.

 

Ŷ

Switch the AC circuit breakers to the OFF (O) position.

 

Ŷ

Start the engine. (refer to “STARTING THE ENGINE” 
section)

 

Ŷ

Switch the AC circuit breakers to the ON ( I ) position.

 

Ŷ

Plug in the appliance.

DC OPERATION

WARNING:

Do not use to charge automotive batteries. 

STARTING THE ENGINE (RECOIL)

See Figures 13 - 15.

NOTE: 

If location of generator is not level, the unit may not 

start or may shut down during operation.

 

Ŷ

Turn the fuel valve to the ON position.

 

Ŷ

Move the choke lever to the START position.

NOTE: 

If engine is warm or the temperature is above 

Û&SXVKWKHFKRNHOHYHULQWRWKH581SRVLWLRQ

 

Ŷ

Put the engine switch in the ON ( I ) position.

 

Ŷ

Turn the key to ON position.

 

Ŷ

Pull the recoil starting grip until the engine runs (a maximum 
of 6 times).

NOTE: 

Do not allow the grip to snap back after starting; 

return it gently to its original place.

 

Ŷ

Allow the engine to run for 30 seconds, then move the 
choke lever in to the RUN position.

STARTING THE ENGINE (ELECTRIC)

 

Ŷ

Turn the fuel valve to the ON position.

 

Ŷ

Move the choke lever to the START position.

NOTE: 

If engine is warm or the temperature is above 

Û&SXVKWKHFKRNHOHYHULQWRWKH581SRVLWLRQ

 

Ŷ

Put the engine switch in the ON ( I ) position.

 

Ŷ

Turn the key to ON position.

 

Ŷ

Turn the key to “START” position and release.

 

Ŷ

Allow the engine to run for 30 seconds, then move the 
choke lever in to the RUN position.

REMOVABLE CONTROL PANEL

The removable control panel can be wall-mounted and 
connected to the generator with the 7.6 m (25 ft.) power cord         
(Model # RDEC25) provided with the product.

The generator can be turned OFF from the removable control 
panel or the off s

witch on the unit.

NOTE: 

You must push the off switch and hold it until the engine 

has fully stopped.
The removable control panel has two 240V 15A sockets.
Use only with RDEC25 accessory cord. Do not exceed 
separation length of 22.9 m (75 ft.) or a combination of three 
RDEC25 accessory cords.

GenSmart MONITORING SYSTEM

The GenSmart monitoring system displays wattage, voltage, 
hertz, and hours. To cycle through each display, press and 
release the select/reset button.

Load Indicator 

Measures the wattage output of the removable control panel. 

Hour Meter

The digital hour meter operates whenever the engine is running 
and keeps track of how many hours the unit has been used. 
Use this meter along with the accompanying engine manual to 
determine when and what type of service on the unit is needed. 
To display, press and release the select/reset button to cycle 
through the displays until HRS appears.

Maintenance Warning System

At every 100 hours of use, the GenSmart™ monitoring 
system will display a flashing message informing the operator 
to service the engine as required by the engine operator’s 
manual. To reset this message, push and hold the select/
reset button located underneath the GenSmart™ display for 
5 seconds.

NOTE: 

Be careful to only press and hold the reset button when 

you want the maintenance panel to be reset.

OPERATING THE GENERATOR USING THE WALL-
MOUNTED REMOVABLE CONTROL PANEL

See Figures 11-12.

If the panel has been installed in a remote location:

 

Ŷ

Turn off the generator.

 

Ŷ

Connect the generator to the removable control panel 
using the twist-lock plug and the 12 Volt DC engine control 
connector on the provided power cord.

 

Ŷ

ONLY use a generator outdoors and far away from open 
windows, doors, and vents. These openings can pull in 
generator exhaust.

 

Ŷ

Connect up to two additional 7.6 m (25 ft.) extension 
cords to the provided 7.6 m (25 ft.) power cord. The total 
length of all connected power cords should not exceed                      
22.9 m  (75 ft.) or three (3) RDEC25 extension cords.

 

Ŷ

Connect the extension cord to the generator.

 

Ŷ

Start the engine as described in 

Starting the Engine

.

 

Ŷ

Add devices to the generator and monitor the load of each 
added device using the GenSmart™ display panel.

STOPPING THE ENGINE

See Figures 13- 14.

 

Ŷ

To stop the engine under normal operating conditions:

 

Ŷ

Remove any load from the generator.

 

Ŷ

Switch the AC circuit breakers to the off position.

 

Ŷ

Disconnect DC battery charging cables.

 

Ŷ

Turn the fuel valve to the OFF position.

 

Ŷ

Put the engine switch in the OFF ( O ) position, and hold 

Содержание AGN6500

Страница 1: ......

Страница 2: ... with foot Lock Nut Lock Nut Flat Washer Frame Frame crossbar Screw 1 in Engine Switch AC Breaker DC Breaker Key Starter Fuel Tank Oil Drainage Bolt Fuel Cap Choke Lever Fuel Valve Oil Light Air Filter Recoil Starter Grip Carburetor Drain Screw Fig 1 Fig 5 Fig 3 Fig 2 Fig 4 ...

Страница 3: ...3 3 Fuel Tank Fuel Cap Extension Cord Oil Cap Dipstick Oil Cap Dipstick Oil Fill Hole Oil Fill Hole 108 mm 4 1 4 in 16 mm 5 8 in 6 mm 1 4 in Fig 7 Fig 6 Fig 10 Fig 11 Fig 8 Fig 9 ...

Страница 4: ...ments Air Filter Cover Bolt Bolt Recoil Starter Grip Twist lock Receptacle Extension Cord Twist lock Plug Choke Lever To Run Choke open To Start Choke closed OFF ON Fuel Valve Fuel Valve Filter Filter Fig 17 Fig 13 Fig 14 Fig 15 Fig 16 Fig 12 ...

Страница 5: ...ose fuel valve and restrain the unit from moving before transporting in a vehicle Ŷ Allow engine to cool for five minutes before refueling Ŷ To reduce the risk of fire and burn injury handle fuel with care It is highly flammable Ŷ Do not smoke while handling fuel Ŷ Store fuel in a container approved for unleaded fuel Ŷ Position the unit on level ground stop engine and allow to cool before refuelin...

Страница 6: ...tand completely the operator s manual If you do not understand the warnings and instructions in the operator s manual do not use this product Call your nearest authorised service centre for assistance WARNING The operation of any products can result in foreign objects being thrown into your eyes which can result in severe eye damage Before beginning power tool operation always wear safety goggles ...

Страница 7: ...l Surge Starting Watts CD Player 100 0 Space Heater 1800 0 Drill 1 2 HP 600 300 Light Bulb 75 0 2575 Total Running Watts 300 Surge Watts Total Continuous Running Watts 2575 Plus Additional Surge Watts 300 Equals Total Generator Output Required to start all items simultaneously 2875 POWER MANAGEMENT To prolong the life of the generator and attached devices it is important to take care when adding e...

Страница 8: ...p protect against electrical shock Consult with a local electrician for grounding requirements in your area OIL LIGHT The oil light is an indicator for the oil level When the oil level is too low the oil light will flash in red OIL DRAINAGE BOLT When changing the engine oil the oil drainage bolt is loosened to allow old engine oil to be drained OIL CAP DIPSTICK Remove the oil fill cap to check and...

Страница 9: ...the following items 2 legs with rubber feet 6 flat washers 6 lock nuts 4 screws 51 mm 2 in 2 screws 25 mm 1 in Ŷ Raise the front end of the generator where the engine is located high enough to gain access to the frame bottom securely position props underneath to support Ŷ Position a leg over the holes on each side of the frame support Ŷ Insert each 51 mm 2 in screw through a flat washer and insert...

Страница 10: ...ty with tools to make you careless Remember that a careless fraction of a second is sufficient to inflict serious injury WARNING Do not use any attachments or accessories not recommended by the manufacturer of this product The use of attachments or accessories not recommended can result in serious personal injury APPLICATIONS This generator is designed to supply electrical power for operating comp...

Страница 11: ...nd hold it until the engine has fully stopped The removable control panel has two 240V 15A sockets Use only with RDEC25 accessory cord Do not exceed separation length of 22 9 m 75 ft or a combination of three RDEC25 accessory cords GenSmart MONITORING SYSTEM The GenSmart monitoring system displays wattage voltage hertz and hours To cycle through each display press and release the select reset butt...

Страница 12: ...p dipstick NOTE Used oil should be disposed of at an approved disposal site See your local oil retailer for more information FUEL FILTER The fuel filter prevents dirt and water that may have gotten into the fuel tank from entering the carburetor If the engine has not been run for a long time the fuel filter should be replaced before use Ŷ Drain the fuel tank into suitable container Ŷ Squeeze the e...

Страница 13: ... fuel to drain completely into the container Ŷ Retighten the drain screw NOTE After draining the fuel tank and carburetor start the engine and allow it to run until the unit runs out of fuel Consult hazardous waste management guidelines in your area for the proper way to dispose of used fuel TRANSPORTING Ŷ Turn engine switch OFF O Ŷ Close the fuel valve Ŷ Make sure engine and exhaust of unit is co...

Страница 14: ...ated to extend storage life For recommendations contact your nearest authorised service centre MAINTENANCE SCHEDULE Before each use After 1st month or 20 hours of operation Every 3 months or 50 hours of operation Every 6 months or 100 hours of operation Every year or after 300 hours of operation Check Engine Oil Ŷ Change Engine Oil Ŷ Ŷ Check Air Filter Ŷ Clean Air Filter Ŷ Change Air Filter Ŷ Repl...

Страница 15: ...er is OFF Item plugged in is defective Turn ON the AC circuit breaker Try a different item Generator makes a spark knock or pinging noise An occasional light knocking or pinging underheavyloadisnotacause for concern However if the knocking or pinging occurs under normal load at a steady engine speed the problem may be with the brand of unleaded fuel being used Switch to a different brand of unlead...

Страница 16: ...ING DIAGRAM 7KLV VLQJOH SKDVH JHQHUDWRU LV WWHG ZLWK D HG 5HVLGXDO XUUHQW HDUWK OHDNDJH HYLFH ZLWK ZLQGLQJ FRQQHFWHG DV VKRZQ LQ WKH following wiring diagram Generator Residual Current Device Outlet Frame A N E ...

Страница 17: ...17 17 WIRING DIAGRAM ...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: