Page 12
PS QuarterHorse Series Chillers
Process Water Bypass
All PS chillers have an internal bypass device. If the process flow becomes blocked
during chiller operation, this component allows water to flow through the chiller. This
protects the chiller from freeze-up, excessive pressures, and pump damage, and allows
other safety features to remain effective.
2-3 PS Condenser Air Supply
PS chillers use the surrounding air to cool the condenser.
;
Condenser air entering the PS unit should be at least 65
°
F (18
°
C). Operation
with air below 65
°
F (18
°
C) can cause the chiller to have low refrigerant
pressure.
;
Install the chiller in an area where there is free passage of air for
condensing.
;
Provide 18” (46 cm) or more clearance for the chiller’s air intake.
;
Make provisions to exhaust the heated air discharged from the chiller.
;
Do not put the PS unit where steam, hot air or fume exhausts will be drawn
into the condenser.
;
Air-cooled condensers must be cleaned frequently. Neglect reduces
capacity, increases operating costs, and leads to possible chiller failure. See
Chapter 6 on Page 21 for cleaning instructions.
;
Normal condensing pressure with 95
°
F (35
°
C) air is approximately 180 psi
(1,241 kPa).
PS Ambient Temperature Ranges
Ambient temperature range
Minimum temperature
Maximum temperature
Operation
65°F (18°C)
100°F (38°C)
Storage
40°F (4°C)
120°F (49°C)
2-4 Water Reservoir
During startup and when additional solution is required, see Figure 3 on Page 14 for the
recommended ethylene glycol/water solution. This chart shows the proportions needed
to provide freeze protection to 20
°
F/11
°
C below the desired process set point.
;
Add a pre-mixed solution to provide freeze protection to a temperature 20
°
F/11
°
C below the normal operating temperature of the chiller.
;
Use industrial quality (
not
automotive) ethylene glycol.
;
A corrosion inhibitor suitable for the materials in the system should be
added to the glycol/water solution.
Содержание QuarterHorse Series 0.25 Portable Chiller PS-025
Страница 1: ...PS 025 QuarterHorse Series 0 25 hp Portable Chiller Operation and Installation Manual...
Страница 16: ...Page 16 PS QuarterHorse Series Chillers Notes...
Страница 17: ...PS 025 QuarterHorse Series 0 25 hp Portable Chiller Operation and Installation Manual...
Страница 18: ...Page 18 PS QuarterHorse Series Chillers Notes...
Страница 20: ...Page 20 PS QuarterHorse Series Chillers Notes...
Страница 22: ...Page 22 PS QuarterHorse Series Chillers Notes...
Страница 24: ...Page 24 PS QuarterHorse Series Chillers Service Notes...
Страница 25: ...PS QuarterHorse Series Chillers Page 25 Service Notes...
Страница 28: ...801 AEC Drive Wood Dale IL 60191 1198 USA 630 595 1060 Fax 630 595 6641 http www aecinternet com...