4KVA 

10 AWG 

1.4~ 1.6Nm 

5KVA 

8 AWG 

1.4~ 1.6Nm 

 

Please follow below steps to implement AC input/output connection: 
1.

 

Before making AC input/output connection, be sure to open DC protector or disconnector first. 

2.

 

Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.   

3.

 

Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be 
sure to connect PE protective conductor (

first. 

Ground (yellow-green) 

L

LINE (brown or black) 

N

Neutral (blue) 

 

 

WARNING:   

Be sure that AC power source is disconnected before attempting to hardwire it to the unit. 

 

4.

 

Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. 
Be sure to connect PE protective conductor (

first.   

Ground (yellow-green) 

L

LINE (brown or black) 

N

Neutral (blue) 

 

5.

 

Make sure the wires are securely connected. 

 

 

CAUTION: Important 

Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause 
utility short-circuited when these inverters are worked in parallel operation. 

CAUTION:

 Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required 

to have enough time to balance refrigerant gas inside of circuits.    If a power shortage occurs and recovers in a 
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check 
manufacturer  of  air  conditioner  if  it’s  equipped  with  time-delay  function  before  installation.  Otherwise,  this 
inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes 
internal damage to the air conditioner.

 

www.

ADVICE

.co.il

e-mail:advice@advice.

co.il

Содержание OGMKS 1KVA-5KVA

Страница 1: ...OGMKS 1KVA 5KVA INVERTER CHARGER User Manual www ADVICE co il e mail advice advice co il...

Страница 2: ...tion 8 Final Assembly 9 OPERATION 10 Power ON OFF 10 Operation and Display Panel 10 LCD Display Icons 11 LCD Setting 13 Display Setting 17 Operating Mode Description 20 Fault Reference Code 22 Warning...

Страница 3: ...device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow required spec to select appropriate cable size It s very important to correctly opera...

Страница 4: ...ing Configurable AC Solar Charger priority via LCD setting Compatible to mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circuit protection Smart b...

Страница 5: ...tor 3 Charging indicator 4 Fault indicator 5 Function buttons 6 Power on off switch 7 AC input 8 AC output 9 PV input 10 Battery input 11 Circuit breaker 12 RS232 communication port 13 Parallel commun...

Страница 6: ...ting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display to be read at all time...

Страница 7: ...mportant for system safety and efficient operation to use appropriate cable for battery connection To reduce risk of injury please use the proper recommended cable and terminal size as below Recommend...

Страница 8: ...on the terminals before terminals are connected tightly CAUTION Before making the final DC connection or closing DC breaker disconnector be sure positive must be connected to positive and negative mus...

Страница 9: ...ive conductor first Ground yellow green L LINE brown or black N Neutral blue 5 Make sure the wires are securely connected CAUTION Important Be sure to connect AC wires with correct polarity If L and N...

Страница 10: ...oc of PV modules not exceeds max PV array open circuit voltage of inverter 2 Open circuit Voltage Voc of PV modules should be higher than min battery voltage Solar Charging Mode INVERTER MODEL 1KVA 24...

Страница 11: ...Plus 4KVA 5KVA Communication Connection Please use supplied communication cable to connect to inverter and PC Insert bundled CD into a computer and follow on screen instruction to install the monitor...

Страница 12: ...tput power information LED Indicator LED Indicator Messages Green Solid On Output is powered by utility in Line mode Flashing Output is powered by battery or PV in battery mode Green Solid On Battery...

Страница 13: ...oad in VA and load in Watt Battery Information Indicates battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode In AC mode it will present battery charging statu...

Страница 14: ...1 95 2 033V cell 2 033 Load Information Indicates overload Indicates the load level by 0 24 25 50 50 74 and 75 100 0 25 25 50 50 75 75 100 Mode Operation Information Indicates unit connects to the ma...

Страница 15: ...ltage Utility first default Utility will provide power to the loads as first priority Solar and battery energy will provide power to the loads only when utility power is not available SBU priority Sol...

Страница 16: ...e output of inverter will be off when connected load is pretty low or not detected 05 Battery type AGM default Flooded User Defined only available in 4K 5K model If User Defined is selected battery ch...

Страница 17: ...KVA 48V models 2A 10A 20A 30A default 12 Setting voltage point back to utility source when selecting SBU priority in program 01 Available options in 24V models 22 0V 22 5V 23 0V default 23 5V 24 0V 24...

Страница 18: ...tery Solar energy will charge battery if it s available and sufficient 18 Alarm control Alarm on default Alarm off 19 Auto return to default display screen Return to default display screen default If...

Страница 19: ...e fixed to setting value no matter what percentage of load is connected Then low DC warning voltage is 2V higher than cut off voltage low DC warning return voltage is 4V higher than cut off voltage an...

Страница 20: ...ercent 70 Charging current Output voltage Current 10A Current 10A Input voltage Load in VA When connected load is lower than 1kVA load in VA will present xxxVA like below chart When load is larger tha...

Страница 21: ...ll present xxxW like below chart When load is larger than 1kW 1KW load in W will present x xkW like below chart Main CPU version checking Main CPU version 00014 04 Secondary CPU version checking Secon...

Страница 22: ...by the unit but it still can charge batteries Charging by utility Charging by PV energy No charging Fault mode Note Fault mode Errors are caused by inside circuit error or external reasons such as ove...

Страница 23: ...It will also charge the battery at line mode Charging by PV energy Charging by utility Battery Mode The unit will provide output power from battery and PV power Power from battery and PV energy Power...

Страница 24: ...s abnormal For 1K 2K 3K model Output voltage is too high For 4K 5K model 07 Overload time out 08 Bus voltage is too high 09 Bus soft start failed 11 Main relay failed 51 Over current or surge 52 Bus v...

Страница 25: ...Battery is over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds 12 Solar charger stops d...

Страница 26: ...Voltage 270Vac 7V Max AC Input Voltage 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High Loss Return Fr...

Страница 27: ...110 150 load Surge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 24Vdc 48Vdc Cold Start Voltage 23 0Vdc 46 0Vdc Low DC Warning Voltage load 20 22 0Vdc 44 0Vdc 20 load 50 21 4Vdc 42 8V...

Страница 28: ...ant Current Absorption Constant Voltage Maintenance Floating Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc Solar Charging Mode INVERTER MODEL 1KVA 24V 2KVA 24V 3KV...

Страница 29: ...Plus 3KVA 24V Plus 2KVA 48V Plus 3KVA 48V Plus 4KVA 5KVA Safety Certification CE Operating Temperature Range 0 C to 55 C Storage temperature 15 C 60 C Dimension D W H mm 128 x 272 x 355 140 x 295 x 4...

Страница 30: ...Ds are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is overload 110 and time is up R...

Страница 31: ...112 269 1200 95 227 1400 81 176 1600 62 140 1800 55 125 2000 50 112 3KVA 300 449 1100 600 222 525 900 124 303 1200 95 227 1500 68 164 1800 56 126 2100 48 108 2400 35 94 2700 31 74 3000 28 67 Model Lo...

Страница 32: ...3 2400 91 219 2700 71 174 3000 63 155 4KVA 400 766 1610 800 335 766 1200 198 503 1600 139 339 2000 112 269 2400 95 227 2800 81 176 3200 62 140 3600 55 125 4000 50 112 5KVA 500 613 1288 1000 268 613 15...

Отзывы: