14
10A (Not available
for 2-3KVA 24V Plus)
20A
30A
40A
50A
60A (default)
03
AC input voltage range
Appliances (default)
If selected, acceptable AC input
voltage range will be within
90-280VAC.
UPS
If selected, acceptable AC input
voltage range will be within
170-280VAC.
04
Power saving mode
enable/disable
Saving mode disable
(default)
If disabled, no matter connected load
is low or high, the on/off status of
inverter output will not be effected.
Saving mode enable
If enabled, the output of inverter will
be off when connected load is pretty
low or not detected.
05
Battery type
AGM (default)
Flooded
User-Defined
(only available in
4K/5K model)
If “User-Defined” is selected, battery
charge voltage and low DC cut-off
voltage can be set up in program 26,
27 and 29.
06
Auto restart when overload
occurs
Restart disable
(default)
Restart enable
07
Auto restart when over
temperature occurs
Restart disable
(default)
Restart enable
09
Output frequency
50Hz (default)
60Hz
11
Maximum utility charging
current
Available options in 1KVA 24V model:
10A
20A(default):
Available options in 2-3KVA 24V and 2-3KVA 24V Plus models: