14
EKI-6233BN User Manual
2.2.5
Power Connection
2.2.5.1
Overview
The gateways can be powered by using the same DC source used to power other
devices. A DC voltage range of 12 to 48 V
DC
must be applied between the V1+
terminal and the V1- terminal (PW1), see the following illustrations. The chassis
ground screw terminal should be tied to the panel or chassis ground. A redundant
power configuration is supported through a secondary power supply unit to reduce
network down time as a result of power loss.
EKI-6233BN support 12 to 48 V
DC
. Dual power inputs are supported and allow you to
connect a backup power source.
Figure 2.13 Power Wiring for EKI-6233BN
Warning!
Power down and disconnect the power cord before servicing or wiring
the gateway.
Caution!
Do not disconnect modules or cabling unless the power is first
gatewayed off.
The device only supports the voltage outlined in the type plate. Do not
use any other power components except those specifically designated
for the device.
Caution!
Disconnect the power cord before installation or cable wiring.
P2 P1
Chassis
GND
(pane)
One DC Supply
P2 P1
Chassis
GND
(pane)
Dual DC Supplies
Single DC Power
Redundant DC Power