Appendix A RS-485 Network
ADAM-5510KW Series User’s Manual A-
7
Figure A-5: Termination resistor locations
Because each input is biased to 2.4 V, the nominal
common mode voltage of balanced RS-485 systems, the
18 k
on the input can be taken as being in series across
the input of each individual receiver. If thirty of these
receivers are put closely together at the end of the
transmission line, they will tend to react as thirty 36k
resistors in parallel with the termination resistor. The overall
effective resistance will need to be close to the
characteristics of the line. The effective parallel receiver
resistance R
P
will therefore be equal to:
R
P
= 36 x 10
3
/30 = 1200
Ω
While the termination receptor R
T
will equal:
R
T
= R
O
/ [1 - R
O
/R
P
]
Thus for a line with a characteristic impedance of 100
resistor R
T
= 100/[1 - 100/1200] = 110
Ω
Since this value lies within 10% of the line characteristic
impedance.
Содержание ADAM-5550KW Series
Страница 1: ...ADAM 5550KW Series Programmable Automation Controller User s Manual...
Страница 6: ...1 System Overview...
Страница 23: ...2 Installation Guidelines...
Страница 46: ...3 Quick Start...
Страница 48: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 3 Power wiring System Wiring...
Страница 65: ...Chapter 3 Quick Start 3 20 ADAM 5550KW Series User s Manual 17 Click Exit Setup 18 Click NEXT...
Страница 66: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 21 19 Click NEXT 20 Click Install...
Страница 68: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 23 23 Click Next 24 Click Yes...
Страница 69: ...Chapter 3 Quick Start 3 24 ADAM 5550KW Series User s Manual 25 Click Next 26 Click Next...
Страница 84: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 39 27 Click OK 28 Back to graphical editor...
Страница 90: ...4 Link to Local A Studio For ADAM 5550KWAS...
Страница 127: ...5 Modbus Functions...
Страница 130: ...Chapter 5 Modbus Functions 5 4 ADAM 5550KW Series User s Manual 2 Select ADAM5000TCP_6000 item 3 Click Search button...
Страница 137: ...Chapter 5 Modbus Functions ADAM 5550KW Series User s Manual 5 11 16 Click Contact Network button 17 Double click C002...
Страница 189: ...6 AMONet On line Help...
Страница 193: ...7 Network Functions...
Страница 214: ...Chapter 7 Network Functions 7 22 ADAM 5550KW Series User s Manual 40 Click DO 0 and check the status of DO 0 is ON...
Страница 218: ...Chapter 7 Network Functions 7 26 ADAM 5550KW Series User s Manual Modify Output Range Apply Output Value...
Страница 219: ...Chapter 7 Network Functions ADAM 5550KW Series User s Manual 7 27 Set DO Value Example ADAM 5056 Template...
Страница 242: ...8 Miscellaneous Functions...
Страница 260: ...Appendix A RS 485 Network...
Страница 268: ...Appendix B Grounding Reference...
Страница 275: ...Appendix B Grounding Reference B 8 ADAM 5510KW Series User s Manual Figure B 6 wire impedance...
Страница 286: ...Appendix C Reference Documents...