F-2
ADAM-5510/P31
ADAM-4000/5000 System Grounding Installation
F. 1 Power Supplies For relevant wiring issues,
please refer to the following scheme :
Figure F-1: Grounding Scheme
F.2 Grounding Installation
Ø
The outer case for the module is made of iron and fitted with a fan
and convection holes with filters.
Ø
If possible, wiring should be connected to the module through an
external terminal block (T/B) to avoid external wires directly getting
into the inside of the module. Its advantages are (1) a clear demar-
cation for external/internal wiring responsibility, (2) wire numbering
can be arranged in an explicit and concise manner, and (3) an easy
diagnostics for the wiring problems and a more aesthetical layout
plan.
N F B
P / S
P / S
P / S
N F B
G N D
+ V
P / S
I / O
C
P
U
A D A M 5 0 0 0
D C
A C
N F B
D C 2 4 V
D C 2 4 V
D C 1 0 ~ 3 0 V
E 1 R 1 T 1
Tr3
+
-
MNFB
AC Power Line
E R T
Isolation AC Transformer
To prevent system control from interferences caused by external power
Connect to AI/DI/DO modules (not for Relay output)
The power sources for DI. DO. and AI. should be independent
Only for Relay output
Fan, Light...etc.
Содержание ADAM-5510/P31
Страница 17: ...0 Quick Start...
Страница 38: ...0 22 ADAM 5510 P31 Quick Start...
Страница 39: ...1 Introduction...
Страница 43: ...2 Installation Guidelines...
Страница 52: ...2 10 ADAM 5510 P31 Installation Guideline Figure 2 10 ADAM 5510 P31 network address DIP switch...
Страница 58: ...2 16 ADAM 5510 P31 Installation Guideline...
Страница 59: ...3 System Specifications...
Страница 65: ...4 I O Modules...
Страница 116: ...4 52 ADAM 5510 P31 I O Modules...
Страница 117: ...ADAM 5510 P31 5 1 Chapter 5 5 Troubleshooting...
Страница 129: ...ADAM 5510 P31 A 1 Appendix A A Quick Start Example...
Страница 132: ...A 4 ADAM 5510 P31 Quick Start Example...
Страница 133: ...ADAM 5510 P31 B 1 Appendix B B COM Port Register Structure...
Страница 137: ...ADAM 5510 P31 C 1 Appendix C C Data Formats and I O Ranges...
Страница 147: ...D Performance...
Страница 173: ...E RS 485 Network...
Страница 181: ...ADAM 5510 P31 F 1 Appendix F F ADAM 4000 5000 System Grounding Installation...
Страница 187: ...ADAM 5510 P31 G 1 Appendix G G Grounding Reference...
Страница 202: ...G 16 ADAM 5510 P31 Grounding Reference...