Appendix B
Data Formats and I/O Ranges
B.4.1 Analog Input Ranges - ADAM-5017UH
Range
Code
Input
Range
Data Formats
+Full
Scale
Zero
-Full
Scale
Displayed
Resolution
08h
±10 V
Engineering
+10.000
+00.000
-10.000
1 mV
Two's Comp
0FFF
0
7FFF
1
48h
0 ~ 10 V
Engineering
+10.000
+00.000
-
1 mV
Two's Comp
0FFF
0
Don't care
1
46h
0~20mA
Engineering
+20.000
+00.000
-
1
μ
V
Two's Comp
0FFF
0
Don't care
1
07h
4~20mA
Engineering
+20.000
+00.000
-
1
μ
V
Two's Comp
0FFF
0
Don't care
1
Note:
The full scale values in this table are theoretical values for your
reference; actual values will vary.