![Advantech ADAM-5000/TCP Series Скачать руководство пользователя страница 132](http://html1.mh-extra.com/html/advantech/adam-5000-tcp-series/adam-5000-tcp-series_manual_2857301132.webp)
Planning Your Application Program
Chapter 6
Response !aa(cr)
if the command is valid.
?aa(cr)
if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
!
delimiter character indicating a valid command was
received.
?
delimiter character indicating the command was in-
valid.
aa
(range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(cr)
is the terminating character, carriage return (0Dh)
Example
command:
$01S3A0000(cr)
response:
!01(cr)
The analog input module in slot 3 of the ADAM-
5000/TCP system at address 01h is configured to an
input range ±15mV, engineering units data format, and
integration time 50ms (60Hz). The response indicates
that the command has been received.
Note:
An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it is reconfigured.
During this time span, the module cannot be addressed to per-
form any other actions.
ADAM-5000/TCP
User’s Manual
6-65
Содержание ADAM-5000/TCP Series
Страница 1: ......
Страница 23: ......
Страница 44: ...4 I O modules...
Страница 148: ......
Страница 183: ......
Страница 218: ......
Страница 300: ...Appendix A Design Worksheets...
Страница 307: ...Appendix A Design Worksheets A 8 ADAM 5000 TCP User s Manual...
Страница 308: ...Appendix B Data Formats and I O Ranges...
Страница 323: ...Appendix B Data Formats and I O Ranges B 13 ADAM 5000 TCP User s Manual...
Страница 324: ...Appendix C Grounding Reference...
Страница 331: ...Appendix C Grounding Reference Figure C 6 wire impedancC C 8 ADAM 5000 TCP User s Manual...