Planning Your Application Program
Chapter 6
01h. Channels 2, 4, 5, 9 and 12 will be set to ON, and
all other channels are set to OFF.
command:
#01S0003A(cr)
response:
>(cr)
An output byte with value 3Ah
(00111011) is sent to the digital output module
(ADAM-5060) in slot 0 of the ADAM-5000/TCP
system at address 01h. Chan- nels 0, 1, 3, 4 and 5 will
be set to ON while channel 2 is set to OFF.
Bits 6 and 7 are not used and always default to 0.
Note: If any channel of the digital output module is configured as
the output for an analog input alarm, it cannot be reconfigured
via digital output commands. Channels used for analog input
alarms
always have a higher priority.
ADAM-5000/TCP
User’s Manual
6-145