Remote Condensers
Page: 5
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
www.AdvantageEngineering.com
E.
Units in Pits
1.
The top of the condenser must be level with, or above the top of the pit.
2.
A minimum of 8 feet (2.25m) is required between the unit and the pit walls.
F.
Multiple Units
1.
A minimum of 8 feet (2.25m) is required between multiple units placed side by
side.
2.
If the units are placed end to end the minimum distance between each unit is 4
feet (1.25m).
G. Louvers/Fences
1.
Louvers/fences must have a minimum of 80% free areas and 4 feet (1.25m)
clearance between the unit and louvers/fence.
2.
Height of louver/fence must not exceed top of the unit.
Minimum
4 ft
(1.25 m)
Minimum
8 ft
(2.5 m)
Minimum
8 ft
(2.5 m)
Minimum
8 ft
(2.5 m)
Minimum
4 ft
(1.25 m)
Minimum
4 ft
(1.25 m)