background image

Remote Condensers

Page: 7

Advantage Engineering, Inc.

525 East Stop 18 Road Greenwood, Indiana 46142 

317-887-0729    Fax: 317-881-1277

Service Department Fax:  317-885-8683

www.AdvantageEngineering.com

G. 

Lifting holes have been provided at the corners or along sides for attaching lifting slings. 

Spreader bars must be used when lifting so that lifting forces are applied vertically. If 

more than 4 lifting holes are provided on the condenser, more than four lifting points 

should be used.

2.3  REFRIGERANT PIPING

A. 

All refrigerant piping must be installed by a qualified refrigerant mechanic. 

B. 

The importance of correct refrigerant pipe sizing and layout cannot be over-emphasized. 

Failure to observe proper refrigerant piping practices can result in equipment failure 

which may not be covered under warranty.

C. 

All air-cooled condensers are supplied complete with headers and refrigerant connections 

sized for connecting the standard refrigeration tubing.

D. 

These connections may bot be the same as the actual line sized required for the field 

installation. Refer to a recognized source (ASHRAE charts, manufacturer’s engineering 

manuals etc) for line sizing.

2.4  DISCHARGE LINES

A. 

The proper design of discharge lines minimizes refrigerant pressure drop since high 

pressure losses increase the required compressor horsepower per ton of refrigeration. 

B. 

A discharge check-valve at the bottom of a vertical riser will prevent oil (and liquid 

refrigerant) from draining back to the compressor during the off-cycle. A check valve may 

be factory or field supplied.

C. 

A reverse trap should be installed at the top of all vertical risers. The top of the reverse 

trap should be the highest point in the discharge line and should have an access valve 

installed to allow the reclamation of non-condensible gas from the system.

Содержание RC Series

Страница 1: ...ATION MAINTENANCE ADVANTAGE ENGINEERING INC 525 East Stop 18 Road Greenwood IN 46142 317 887 0729 fax 317 881 1277 Service Department fax 317 885 8683 www AdvantageEngineering com sales AdvantageEngineering com Model Serial Number AIR COOLED REMOTE OUTDOOR CONDENSER ...

Страница 2: ...317 885 8683 www AdvantageEngineering com TABLE OF CONTENTS 1 0 GENERAL 3 1 1 Receiving Instructions 3 1 2 Introduction 3 1 3 Safety 3 2 0 INSTALLATION 4 2 1 Location 4 2 2 Lifting Instructions 5 2 3 Refrigerant Piping 7 2 4 Discharge Lines 7 2 5 Condensate Lines 8 2 6 Electrical Wiring 8 3 0 OPERATION 9 3 1 System Start Up Checks 9 3 2 Maintenance 9 ...

Страница 3: ...ranty This manual is for standard products The information contained in this manual is intended to be general in nature The information is typical only and may not represent the actual unit purchased C In addition to this manual the condenser manufacturer has supplied a manual specifically for your condenser Refer to the manufacturer s manual for additional and more specific information D When cal...

Страница 4: ... placed away from the chiller B This condenser is designed for outdoor installation It may be installed on a roof or ground level concrete pad The roof or concrete pad must be able to support the operating weight of the condenser C A number of factors must be taken into consideration when selecting a location Most important is the provision for a supply of ambient air to the condenser and removal ...

Страница 5: ...en the unit and the pit walls F Multiple Units 1 A minimum of 8 feet 2 25m is required between multiple units placed side by side 2 If the units are placed end to end the minimum distance between each unit is 4 feet 1 25m G Louvers Fences 1 Louvers fences must have a minimum of 80 free areas and 4 feet 1 25m clearance between the unit and louvers fence 2 Height of louver fence must not exceed top ...

Страница 6: ...es should the coil headers or return bends be used in lifting or moving the condenser D Ensure the unit is placed in a level position to ensure proper drainage of liquid refrigerant and oil E Lower unit into vertical air flow position taking care not to damage coil surface under unit F Attach legs and any angle or cross bracing per manufactures instructions that are included with the condenser The...

Страница 7: ...C All air cooled condensers are supplied complete with headers and refrigerant connections sized for connecting the standard refrigeration tubing D These connections may bot be the same as the actual line sized required for the field installation Refer to a recognized source ASHRAE charts manufacturer s engineering manuals etc for line sizing 2 4 DISCHARGE LINES A The proper design of discharge li...

Страница 8: ...nce with the National Electrical Code and all local codes and regulations B Any wiring diagrams shown are basic and do no necessarily include electrical components which must be field supplied UNIT LOCATED ABOVE OTHER COMPONENTS PRESSURE RELIEF DEVICE SHUT OFF VALVES SEE NOTE 2 CHECK VALVE COMPRESSOR HOT GAS LINES SEE NOTE 1 OIL SEPARATOR PIPING AND COMPONENTS FROM THIS POINT BY OWNER FILTER DRIER...

Страница 9: ...spection preformed by a qualified refrigeration service mechanic WARNING Do not connect the unit to a voltage supply not equal to the unit s voltage requirements as specified on the unit s data plate Use of incorrect voltage will void the unit s warranty and cause a significant hazard that may result in serious personal injury and unit damage WARNING Electric Shock Hazard High Voltage is present i...

Страница 10: ...n power supply must be disconnected to prevent potential hazardous risk C Check the following 1 Check all electrical components for damage Tighten any loose connections 2 Check settings of all controls to ensure proper operation 3 Look for any wear on wires or refrigerant lines that may have been caused by excessive vibrations or rubbing on metal parts 4 Fan motors are permanently lubricate and re...

Страница 11: ...END 2019 ADVANTAGE ENGINEERING INC RE 20191106 ...

Отзывы: