I. Introduction
MICROtron microprocessor based controllers are designed to provide a wide range of control functions for
recirculating water treatment systems. The controller is programmed through a front panel keypad and can
be configured to provide a customized control system for your application. Your particular unit’s functions can
be determined by comparing the units model number to the Model Numbering table listed below.
Model Numbering
MICROtron units have two base models and a few optional features. Your unit may be supplied with one or
more of the features described in this manual. To determine what features apply to your unit check the model
number label located on the controller enclosure. Example: MICRO-C-E3
Base Control Functio
n
Tower Conductivity Control & 3 Feed Timers
C
- TE-4A Standard Tower probe
C0
- Tower Conductivity no probe
C1
- TE-4ASS Standard Tower probe with S. Steel Tips
C3
- AH-4ASS 212°F and 250 PSI max
C5
- DC-4ASS Tank mount with S. Steel Tips
F4
-
4 selectable feed timers only
Whole Unit Optional Features
A
- 100-240 volt conduit connections
A3
- 100-240 volt conduit connections and CE approval
A7
- Australian power cord (240 VAC)
E
- Standard float style flow switch assembly (towers)
E3
- Paddle flow switch with PVC flow assembly
E4
- Paddle flow switch with PVC flow assembly
(unassembled with 10’ cord)
E5
- Paddle flow switch with brass assembly
E6
- Flow switch connection only with cable
E8
- Standard float switch assembly (unassembled with
10’ cord)
E11
- Flow indicator (0-10) assembly w/ adjustable switch
II. Description
MICROtron units are designed to automate conductivity control, the addition of various chemicals, or the
activation of other devices via a relay output.
MICRO-C units include:
* One totalizing water meter input that can be configured for contacting head or hall effect meter inputs.
* Four mechanical relay outputs with normally open and normally closed contacts.
* A “manual relay” timer that allows for manual activation of the relays for a user defined amount of time.
Conductivity Control
(C)
- Conductivity monitoring and control of Total Dissolved Solids (TDS) in a recirculating
water systems in terms of electrical conductivity measured in MicroSiemens/cm. The conductivity scale can
be selected from three ranges (low, mid and high) in the Configure menu (see page 8). Three selectable feed
timers are also included (see timer description below).
Feed Timer
- Selectable timers can be individually programmed as one of the following types:
1.
Pulse Timer
– Accepts dry contact pulses from a water meter (supplied separately). It can accumulate
1-9999 pulses to activate the timer to run from 0-99 minutes, 59 seconds in minutes and seconds.
2.
Recycle Timer
– Provides a user defined “off” cycle in HH:MM and a user defined “on” cycle in
MM:SS that is repeated constantly.
3.
28-Day Timer -
28-day feed timers, typically used for biocide feed are based on a 28-day cycle with
two independent programmable feed cycles allowing for feed on selectable days and weeks.
4. *
Post Bleed Timer -
The relay is activated after a conductivity bleed cycle and runs for the set
percentage of that bleed cycle.
5. *
With Bleed Timer -
Activates the relay output simultaneously with the bleed and limits the amount
of time the relay output will be on during the bleed cycle.
6.
Post Timer -
The relay is activated after the RUN rime of another timer for the set percentage of the
selected timer.
*NOTE: MICRO-F4 timers only have post, pulse, recycle and 28-day timer types available.