Conductivity Sampling Methods
A. Continuous
- Typical for most tower applications. The controller is constantly reading the sensor
and activating the bleed relay based on readings relationship to the set point, set point direction
and differential. Example: A rising set point of 1500 and differential of 50 the bleed relay would
activate when the conductivity rises above 1500 and stays on until the reading drops to 1450.
B. Timed Sampling
- A sample timer allows the conductivity to be sampled at periodic intervals.
Sample intervals are adjustable from 1 minute to 99 hours, 59 min. Sample duration (on-time) is
adjustable from 1 second to 99 minutes, 59 seconds. If the reading is below the set point by the
differential amount the bleed relay will be turned off at the end of the sample duration and the
sample interval countdown started. If the reading is above the set point at the end of the sample
method the bleed relay stays on until the reading drops by the differential amount.
Calibration Overview
The MICRO-C controllers update the conductivity reading every two seconds with a running average. If a probe
is quickly exposed from one extreme reading to another, allow up to 30 seconds for the averaging to cycle
and the current reading to stabilize. MICROtron controller’s conductivity scale should be selected so that the
conductivity setpoint is as close as possible to the middle of the scale. (See page 9 menu for setting scale).
Note: If a controller is using Timed Sampling method of control the conductivity reading shown in the
RUN mode may not be a current reading. The controller will hold and display the conductivity value
seen at the end of the last sample or hold duration. To see a current reading force on the bleed relay
with either the Force button or via the Calibration menu.
A. Continuous
- Calibrating continuous sampling units can be done at any time with the probe in a
steady stream of water with no air or steam present.
B. Timed Sampling
- While in the calibration menu there is a selection to force on the bleed relay.
It will force it into the sample period. After 1-2 minutes verify that the reading is stable then enter
the desired calibration value.
Notes:
1. If you change the conductivity scale in the Configure menu you MUST then go to Diagnostics
and Reset the Cal then go to the Calibration menu and calibrate accordingly.