www.advancedco.com
71
5.7
Appendix 7
– Mx Series Product Capabilities / Max Limits
This section gives details on the maximum capabilities for each of the products in the range. Some of the items
can only be utilised via the PC CONFIG tool and these are annotated accordingly.
Item
5100
5200
5400
5800
5020 /
5030
Mxp-
510
Mxp-
554
Comments
Max № of Loops
1
2
4
8
0
0
0
Max № of Resident Zones
200
200
200
200
26
100
200
200
Highest Resident Zone №
2000
2000
2000
2000
2000
2000
2000
Max № of System Zones
2000
2000
2000
2000
2000
2000
2000
Max № of Points
1000
1000
1000
9
-
-
№ of On-board Points
Depends on optional cards
fitted
№ of On-board Sounders
2
2
4
8
0
0
0
№ of On-board Relays
(including Mxp-507 Card)
2(4)
2(4)
2(4)
4(8)
0
0
0
№ of Switch Inputs
9
9
9
18
9
-
-
Max № of Time Clocks
10
10
10
--
3
3
Max № of Ringing Styles
40
40
40
10
10
10
Max № of Output Groups
200
200
200
200
200
200
Max № of Output Group
Lines
1150
1150
1150
250
250
250
Requires PC CONFIG to
define more than one line
per Output Group
Max № of Passwords
12
12
12
12
12
12
12
Max № of Sectors
Available
100
100
100
100
100
100
100
PC CONFIG Only
Max № of Input Events
250
250
250
100
100
250
PC CONFIG Only
Max № of Logic Blocks
100
100
100
50
50
50
PC CONFIG Only
Max № of Logic Terms
27
1500
1500
1500
100
100
100
PC CONFIG Only
Max First Loop №
99
98
96
96
--
--
--
PC CONFIG Only
26
Per 4-LP Chassis
27
M
ax № of logic terms available to the user depends upon the number of logic blocks defined. Each logic block requires a terminator term. This terminator
uses up one of the available logic terms. Therefore, the number of logic terms available for use will be
the Max № of Logic terms – the № of Logic blocks used –
for example, using 20 logic blocks in an Mx-5400 will give 500-20=480 Logic Terms available to use.
Содержание MxPro 5 Mx-5100
Страница 72: ...www advancedco com 72 This page is intentionally left blank...
Страница 73: ...www advancedco com 73 USER NOTES...