2.5.13.2
FAT / FBF Redundant Connection
Where several FAT terminals need to be connected, or where a redundant connection is required
from several control panels, connect the FAT units via a redundant ring. This requires the installation
of an IFAM ADP-N3E Interface in one panel and (optionally) an IFAM ADP-N3S Interface in a second
panel if required.
for information on mounting options.
Redundant ring adaptors are built into the FAT terminals as standard.
FBF1
TXD
RXD
GND
RS232
FAT1
TXD
RXD
GND
FAT2
FAT3
1 2 3 4
FAT/FBF
RS232
ADP-N3E
0V
TX
RX
TX
RX
0V
1 2 3 4
FAT/FBF
RS232
ADP-N3S
0V
TX
RX
TX
RX
0V
PANEL 1
PANEL n
AUSG
–
AUSG+
–V (27)
+V (26)
U
B
2
+
U
B
2
–
S
IO2
+
S
IO2
–
U
B
1
+
U
B
1
–
S
IO1
+
S
IO1
–
U
B
2
+
U
B
2
–
S
IO2
+
S
IO2
–
U
B
1
+
U
B
1
–
S
IO1
+
S
IO1
–
U
B
2
+
U
B
2
–
S
IO2
+
S
IO2
–
U
B
1
+
U
B
1
–
S
IO1
+
S
IO1
–
U
B
1
+
U
B
1
–
S
IO1
+
S
IO1
–
U
B
2
+
U
B
2
–
S
IO2
+
S
IO2
–
U
B
1
+
U
B
1
–
S
IO1
+
S
IO1
–
U
B
2
+
U
B
2
–
S
IO2
+
S
IO2
–
Both power (24V DC)
and data
communications are
distributed around the
ring.
2.5.13.3
FSD Key Deposit Box Connection
The interface is compatible with IFAM SDA-3000 FSD Adaptor Interface.
SDA-3000
5 6 7 8 9 10
FSD
15
9
10
8
7
13
OPEN
ACK
FIRE
0V
+24V
TAMPER
Key Deposit Box heating power is to be supplied
separately.
Refer to the documentation supplied with the
SDA-3000 for details of the wiring connections
between the interface and the key deposit box
itself.