background image

 

 

www.advancedco.com 

Specifications: 

Models, Sales Order Parts: 

Mxp-035

 

:  4-Way Programmable Relay Card 

Mxp-035-BXP

  :  4-Way Programmable Relay Card Boxed with 1A PSU 

Applications / Limitations: 

Plant Control and Signalling relay outputs.  

Each output can be assigned to an individual output group and is fully programmable for any output function 
allowed within the configuration program. 

Only one 4 Way Relay Output Card can be fitted within an control panel. 

Fitting  of the Mxp-035  in an MxPro 4  panel  precludes fitting of other panel input or output cards. See  panel 
manuals for further information. 

Compatibility: 

Can be used with MxPro 4, MxPro 5 and Axis EN Panels. 

4

200

4400 

and 

4800 

control panels programmed with Version 021-03 software (or later) and fitted with base 

card hardware revision levels 10 (712-1022 Mx-4400) and 09 (712-1022-002 Mx-4200) or later.  

 

Compatible with the PC Configuration Tool from version 4.7 or later.  

 

Requires installation of the Mxp-031 Peripheral Bus Interface Adaptor card in the panel. 

 

 

Item 

Specification Details 

Applicable Standards 

EN54-2: 1997, BS EN54-4: 1997 

Operating Temperature 

-5ºC to 40ºC 

Relative Humidity 

95% non-condensing (maximum) 

Enclosure  

Steel,  IP30,  RAL9002,  320  mm  high  x  345  mm  wide  x  88  mm  deep,  3kg  (excluding 
batteries) 

Knockouts 20mm 

7x Top, 2x Bottom 

AC Supply 

230V AC, 50Hz (+10%, -15%) FUSE T3.15H250 

Standby Battery 

2x12V, 7AH Sealed Lead-Acid Type (Yuasa recommended) 

LED Indications (Box) 

Power  and  General  PSU  Fault 

–  Separate  indications  of  specific  PSU  fault  conditions 

are available on the PSU. 

PCB  

110 mm x 86 mm x 18 mm, 130 grams 

PCB Supply 

24VDC nominal (18-28VDC),  

(quiescent) 22mA (all outputs on) 75mA typical, 100mA maximum 

LED Indications (PCB) 

Relay Circuit ON, Communications TX & RX and Heartbeat 

Outputs (x4) 

230V AC, 5A resistive / 230V AC, ½ HP / 30VDC, 5A 

30VDC, 1A when mounted on panel chassis 

Minimum 20mA wetting current 

EOLR (Fault Input) 

10kΩ 

EOLR (Peripheral Bus) 

150Ω (applied via “485 term” jumper – see section 2.6.3) 

As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice 

 

Содержание Mxp-035

Страница 1: ...output is fully programmable using the powerful DynamiX cause and effects rules and all outputs are synchronised The unit is available as either a printed circuit card only or as a boxed version with...

Страница 2: ...of the Mxp 031 Peripheral Bus Interface Adaptor card in the panel Item Specification Details Applicable Standards EN54 2 1997 BS EN54 4 1997 Operating Temperature 5 C to 40 C Relative Humidity 95 non...

Страница 3: ...6 2 6 WIRING 7 2 6 1 AC Wiring Boxed Units 7 2 6 2 Battery Installation Boxed Unit 7 2 6 3 DC Power and Serial Communications 8 2 6 4 Power Supply Fault Input 8 3 PROGRAMMING AND CONFIGURATION 9 3 1 A...

Страница 4: ...required When All Other Outputs are disabled at the panel all relay outputs attached to the panel are disabled Outputs can also be individually disabled via the user menus or disabled using the group...

Страница 5: ...ircuit card shall be fitted to a metal chassis or in a metal enclosure using the M3 spacers nuts and screws supplied The chassis enclosure must be connected to protective earth Refer to the diagram op...

Страница 6: ...commended routing of cables 2 4 PCB Mounting in a 5000 Panel There is provision on the 5000 chassis plate to mount one peripheral bus module except 5100 small enclosure Refer to panel manual 680 165 f...

Страница 7: ...contact with high frequency interference such as portable radio transceivers etc the data wiring cable should be of a twisted pair construction within a overall screen Care should be taken to correct...

Страница 8: ...or Jumper ON with termination Jumper OFF no termination Peripheral Bus 4 Way Relay Card TB1 A B A B TB2 OUT IN 24V 0V Fault TB7 4 Way Relay Card TB1 A B A B TB2 OUT IN 24V 0V Fault TB7 FIGURE 6 Critic...

Страница 9: ...e and click on the Mxp 035 option to highlight and select it The zone number is pre assigned to the zone number of the panel This can be changed if an alternative zone is required for these circuits S...

Страница 10: ...he button to delete the 4 way relay card from the address 3 3 Configuring the Output Circuits 3 3 1 Basic Details Click the button to show a list of the addresses and sub addresses for all of the devi...

Страница 11: ...group 0 Invert Output Determines if the output is normally OFF not inverted and activates on the event or normally ON inverted and de activates on the event No May Silence Determines if the output wil...

Страница 12: ...dco com Advanced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 133 Re...

Отзывы: