Advanced AxisAX AX-PENN Скачать руководство пользователя страница 17

 

 

www.advancedco.com 

 

17

4  Axis

AX

 Wiring Guide 

Unless otherwise noted, all circuits permitted to be in same conduit. Check local codes for additional restrictions. Twisted shielded 
cable provides a degree of protection and immunity to electrical noise interference (RFI/EMI) compared to twisted pair or untwisted 
wire. If shielded cable is used, connect the shield to the panel enclosure (out and return) and to the dedicated shield terminations in 
the bases only. 

Note:  If shielded cable is utilized, the shield connection must be a continuous circuit around the loop and must not be in 
contact with any other earth/ground point (including electrical back boxes). 

If running NAC and/or 24 VDC circuits in the same conduit as other signals, you can reduce problems by exclusively using electronic 
sounders instead of electronically noisy notification appliances (such as electromechanical bells or horns).  

Circuit Type 

Circuit 

Function 

Wire Types 

Maximum 

Distance 

Typica

l Wire 

Size 

(AWG) 

Comments 

SLC 
(power limited) 
 

Connects to 
intelligent 
modules and 
smoke 
detectors 
 

Twisted Unshielded Pair  
* Maximum resistance is 

dependent on SLC 
loop loading (see note 
#1) 

12,500 feet 
(see note #1) 

12-18 

AWG 

If multiple loops are inside the same conduit it is acceptable to use 
twisted unshielded wire as SLCs will not interfere with one another. It is 
acceptable to run other signals inside the same conduit however, it’s 
recommended that the other wires are either twisted or twisted shielded. 
The Axis

AX

 panels contain loop power technology.  The SLC circuits are 

capable of driving high current loads in alarm, which affects the load 
characteristics including V/I drops along the wire length.  Therefore, it is 
important to utilize Advanced loop calculator in determining wire gauge 
and length. 

Twisted Shielded Pair 

12,500 feet  
(see note 1) 

12 -18 

AWG 

Shield must only be connected to earth ground at one location - at the 
fire panel.  

  

  

 Untwisted, Unshielded 
Pair 
 

 1,000 feet 
(see note 1) 

 

It’s not recommended to mix inside conduit with other signals unless 
other signals use either twisted or twisted shielded wire.  

PBUS 
EIA-485 
(power limited) 

Connects 
peripheral 
modules to 
AX-CTL 
base card 

Twisted Unshielded or 
Twisted Shielded 

5000 feet 

18-20 

AWG 

Twisted unshielded or twisted shielded wire is acceptable whenever the 
PBUS is wired internal and/or external to the fire panel enclosure. Must 
install a 150 ohm resistor at end of the PBUS wire run. When using 
shielded wire, you must install a 2.2 

µ

fd non polarized capacitor from 

shield to ground at one end and terminate shield to panel ground at other 
end. 

EIA-232 
(power limited) 

Connects to 
printers or 
PC 

Shielded  

50 feet 

18-20 

AWG 

 

NACs 
(power limited) 

Connects to 
horns, 
strobes, 
solenoids, 
etc. 

Twisted Shielded, 
Twisted Unshielded, 
Untwisted Unshielded. 

4000 feet 
(see note 2) 

12-22 

AWG 

If supporting highly inductive/noisy loads use twisted shielded wire. 

Network 
EIA-485  
(power limited) 

Ad-NeT-
PluS peer-
to-peer 
network 

Twisted Shielded or 
Fiber Optic Cable 

5000 feet 
  Class B 

66000 feet 
  Class X (A) 
     (5000 ft       
       between 
       Nodes) 

18-20 

AWG 

Fiber Optic – 16,404 ft between nodes max.  Jacket material must be 
rated for application. 
Note that network node to node communications are optically isolated 
and each node has an independent ground fault detection circuit. To 
insure prevention of earth “ground loops”, the shield must be terminated 
at one node and not both. This is accomplished internally at each node 
via dedicated shield terminals.   
Each network node module has isolated outgoing and incoming network 
wiring terminals.  Connect from the “OUT” terminal on the first node to 
the “IN” terminal on the next node (A, B and Shield). 

O

UT 

Shield 


 
 
 

Shield 

I

 

Shield 

 

Telephone 
Riser  (power 
limited) 

Firefighter 
Telephone 
communicati
ons1 to 6 
channels for 
firefighter 
phones 

Twisted Shielded Pair 

 4000 feet 
(see note 3) 

18-20 

AWG 

 

Audio Riser  
(power limited) 

Audio input 
signal to 
amplifiers 

Twisted Shielded Pair 

 4000 feet 

18-20 

AWG 

 

Speaker 
Circuits  
(power limited) 

Speaker 
circuit to 
speakers 

Twisted Pair or Twisted 
Shielded Pair 

 3000 feet 
(load dependant) 

12-22 

AWG 

Twisted shielded wire if mixed inside same conduit as the audio and/or 
telephone riser(s) 

24 VDC 
(power limited) 

24 Volts DC 
resettable or 
non-
resettable 

Untwisted Unshielded, 
Twisted Pair or Twisted 
Shielded Pair 

 4000 feet 

12-18 

AWG 

Size conductors per acceptable voltage drop. If supporting highly 
inductive/noisy loads, twisted shielded wire is recommended. 

Содержание AxisAX AX-PENN

Страница 1: ...www advancedco com AX PENN AX PENN ST7 Peripheral Expansion Network Node Installation Operation Manual...

Страница 2: ...ST7 Class X Ad NeT PluS Network Wiring 8 2 3 2 2 1 Class X Ad NeT PluS Network 9 2 3 3 Peripheral Bus P BUS 9 2 3 3 1 Wiring 10 2 3 4 Optional AX DSP Keyboard Display 10 2 3 5 USB Port 11 2 3 6 RS 23...

Страница 3: ...ripheral bus module remotely from the Axis AX fire alarm control panel i e switch LED modules audio amplifier modules relays etc Each AX PENN or AX PENN ST7 peripheral expansion network node module ca...

Страница 4: ...mounting plate for eventual earth ground connection via the mounting plate enclosure Failure to tighten screws will defeat the protection circuitry designed to protect the card from damage due to ligh...

Страница 5: ...iction requirements in addition to Article 760 of the National Electrical Code NEC Refer to Axis AX Wiring Guide Section 4 SCR B OUT A OUT SCR B IN A IN NETWORK RS485 PERIPHERAL RS485 A OUT B IN A IN...

Страница 6: ...inate with the supplied 3 3K end of line resistor see figure 4 If monitoring an intelligent internal power supply charger i e AX PSU 6 place the supplied 3 3K end of line resistor across the I P SW an...

Страница 7: ...B OUT A OUT SCR B IN A IN NETWORK RS485 PERIPHERAL RS485 A OUT B IN A IN B OUT SW SW PROGRAM COMMISION REBOOT PSU_TX PSU_RX HEARTBEAT USB 232RX USB 232TX DISPLAY ONLY AX PWR FLT USB GND RX TX RS232 F...

Страница 8: ...e minimum twisted shielded pair 18AWG to 20AWG Connect the shield to the designated shield terminals only The IN terminals on the first node and the OUT terminals on the last node are not used Connect...

Страница 9: ...US The AX PENN ST7 can support sixteen 16 of each type of Advanced peripheral bus modules Peripheral bus modules must be located within 20 feet of the AX PENN ST7 module within the same room Below is...

Страница 10: ...is feature is presently not available as existing peripheral bus modules do not support Class A communications 2 3 4 Optional AX DSP Keyboard Display The AX PENN ST7 can support a standard Advanced AX...

Страница 11: ...rt for PC NeT upload download programming see figure 11 2 3 6 RS 232 Port The AX PENN ST7 incorporates an RS 232 output that can be utilized for programming or connection to ancillary reporting device...

Страница 12: ...AxisAX Series Configuration Software 6 81 or higher after installing an AxisAX panel click on the add product icon and select the AxisAX PENN network peripheral If you would like rename the AX PENN fr...

Страница 13: ...NN will also require On Board User Interface and Peripheral Bus programming 3 1 1 Panel Details Programming Within the Panel Details area of the AX PENN the user will need to review and if required mo...

Страница 14: ...oard display the switch input I P SW and SW of the AX PENN and the AC trouble monitoring of an associated AX PSU 6 if intelligently connected 3 1 3 User Interface Programming The User Interface progra...

Страница 15: ...tons and two 2 LEDs associated with the AX PENN ST7 PCB printed circuit board for use in uploading downloading and flashing an AX PENN ST7 module These buttons and LEDs are REBOOT PROGRAM with associa...

Страница 16: ...m panel to PC 4 When uploading downloading is complete exit the commissioning mode by pressing the COMMISION button the COMMISION LED will extinguish 3 2 2 Firmware Updating Procedure To update AX PEN...

Страница 17: ...cts peripheral modules to AX CTL base card Twisted Unshielded or Twisted Shielded 5000 feet 18 20 AWG Twisted unshielded or twisted shielded wire is acceptable whenever the PBUS is wired internal and...

Страница 18: ...ance Circuit The voltage drop on notification appliance circuit should be calculated to ensure that the minimum voltage at the end of the circuit exceeds the minimum required by each notification appl...

Страница 19: ...www advancedco com 19 Examples Number of Firefighter Jacks Phones Max Cable Resistance ohms 5 44 10 34 15 28 20 24 25 21 30 18 35 16...

Страница 20: ...0 USB Lit when USB port active 11 USB RS232 Receive Flashes when data received through USB RS232 12 USB RS232 Transmit Flashes when data sent through USB RS232 13 FTNET HB Style 7 Class X A network he...

Страница 21: ...www advancedco com 21...

Страница 22: ...advancedco com 22 Doc Number 682 059 AFS Revision 1 First Issued 2013 mm dd 100 South Street Hopkinton Massachusetts 01748 Tel 508 435 9995 Fax 508 435 9990 Email usa advancedco com Web www advancedco...

Отзывы: