61180008L1-5B

Section 61180008L1-5, Issue 2

5

Telnet

The SCU will support four concurrent Telnet sessions.
Telnet is supported via the Ethernet interface.

To use Telnet to communicate with the SCU, use the
following steps:

1. Set the proper IP Address for the connection

method of choice via the provisioning menu. For
this procedure, refer to the following page of this
practice.

2. Connect to the Ethernet Interface on the

backplane of the Total Access 1500 shelf.

3. A successful Telnet connection is established

when the following appears on the screen:
/* enter ‘MENUS;’ to obtain menus (characters
will not echo) */
OK 0
<

4. A TL1 session may be activated at this time or to

logon to the Total Access Menu System, enter
‘MENUS;’.  If Password authentication is
enabled, enter the Account Name for the Total
Access shelf, and press ENTER. The cursor will
then be placed at the Password field, waiting for
a password.

5. At the Password field, enter the Password for the

Total Access System, and press ENTER.

6. Upon entering the correct password, the Total

Access main menu is presented on the screen.
This signifies a successful logon.

Provision the Ethernet Interface Settings

If the Total Access 1500 shelf is to be connected to an
Ethernet network for Telnet, TFTP or SNMP
Management, the IP Address, Subnet Mask, and
Default Gateway must be set for the shelf to
communicate with the network.

To set the IP Address, Subnet Mask, and Gateway:

1. From the System Controller main menu, select

option 5, Management Configuration, and press
ENTER.

2. From the Management Configuration menu,

select option 1, IP Address, and press ENTER.

NOTE

The IP Address, Subnet Mask and Gateway are
in  the  form  XXX.XXX.XXX.XXX,  with  the
XXX’s  representing  1,  2  or  3  digit  decimal
numbers from 0 to 255.

3. Enter a valid IP address, and press ENTER.

4. From the Managemen  Configuration menu,

select option 2, IP Subnet Mask, and press
ENTER.

5. Enter a valid Subnet Mask, and press ENTER.

6. From the Management Configuration menu,

select option 3, IP Default Gateway, and press
ENTER.

7. Enter a valid Default Gateway, and press

ENTER.

8. From the Management Configuration menu,

select option 4, Telnet Port Number, and press
ENTER.

9. Enter the port to connect to when performing

TL1 over TCP/IP.  This is set to 2000 as a
default.

Menuing System

The ADTRAN Total Access SCU provides a menuing
system for the Total Access shelf. All system-related
menus are controlled by the SCU as well as some of
the access modules menus. Other access modules have
their own user menu structure supported by the
module.

Menu Structure

The menu structure for the SCU is a layered menu
tree. Each menu level consists of submenus and/or
menu items. Some menu items are restricted to certain
user accounts. The SCU supports Read-Write and
Read-Only accounts.  Each of these accounts may also
be given Test or Admin privileges.  The Admin
privileges allow the user to change all provisionable
settings as well as network configuration settings that
are not accessible to Read-Write and Read-Only
accounts. Examples include SNMP provisioning, TL1
provisioning, Date/Time settings, password
administration, and software downloads. The
Read-Write account allows the standard provisioning
settings to be changed. The Read-Only account allows

Содержание Total Access 1500 SCU

Страница 1: ...ry This is the second release of this document This version includes updates describing TL1 over X 25 and TCP IP Features The Total Access 1500 SCU P Ns 1180008L1 1180008L2 and 1180008L3 includes the...

Страница 2: ...static packing material when transporting or storing The Total Access 1500 SCU plugs directly into the SCU slot in the common module area of the Total Access 1500 chassis WARNING TheTotalAccess1500SCU...

Страница 3: ...m r e T a t a D R T D 5 d n u o r G l a n g i S X 25 Port The SCU supports synchronous RS 232 compatible serial interface to be used in conjunction with an X 25 network The unit includes PAD functions...

Страница 4: ...session or a Telnet session VT100 Terminal To connect either a terminal or a PC emulating a terminal to the craft port 1 Set the parameters of the VT100 terminal to 9600 baud rate NOTE The SCU craft...

Страница 5: ...m the Management Configuration menu select option 1 IP Address and press ENTER NOTE The IP Address Subnet Mask and Gateway are in the form XXX XXX XXX XXX with the XXX s representing 1 2 or 3 digit de...

Страница 6: ...32 shelves may be clustered together via the RS 485 bus To set up RS 485 chaining perform the following 1 Give the first SCU in the chain a unique Target ID TID 2 Enable RS 485 Interface 3 Set Interba...

Страница 7: ...Local 1 SCU 2 Online LIU 1 Select Y Modem Upload Destination 3 Modify Checksum 2 Start Y Modem Upload 5 Reset the Y Modem Destination 4 Compute Checksum and Store Unit Name Part Number CLEI Code Prod...

Страница 8: ...the Total Access 1500 shelf The following alarm inputs are supported Alarm Wire wrap Header Auxiliary 1 AUX 1 Auxiliary 2 AUX 2 Alarm Cut Off AUX 3 Remote AUX 4 NOTE The front panel mounted ACO switc...

Страница 9: ...m u H e v i t a l e R g n i s n e d n o c n o n C 0 5 m u m i x a m 5 9 n o i t a p i s s i D t a e H m u m i x a m s t t a w 4 2 4 e c n a i l p m o C 0 5 9 1 L U 3 l e v e L S B E N E R O C 9 8 0 1...

Страница 10: ...mer and Product Service CAPS prior to returning equipment to ADTRAN For service CAPS requests or further information contact one of the following numbers ADTRAN Sales Pricing Availability 800 827 0807...

Отзывы: