Troubleshooting
61287722G1-5B
41
UPS Communication Signals
The
communication
signals
of
the
UPS
are
isolated
from
the
internal
circuitry
via
open
collector
opto
‐
coupled
transistors.
The
connection
SIG RTN
(Signal
Return)
is
a
common
return
point
for
all
communication
signals.
In
the
typical
application,
the
attached
equipment
digital
ground
connects
to
Signal
Return,
and
pull
‐
up
resistors
turn
the
open
collector
signals
into
logic
levels.
A
pinout
of
the
communication
signals
is
shown
in
Table 13. UPS Communication Signal Descriptions
Signal
Description
+12
VDC
Vo+
(+
Voltage
output)
12
V
RTN
Return
path
for
+12
VDC
SIGNAL
RETURN
Signal
return
ON
BATTERY
Low
when
operating
from
utility
line
Open
when
operating
from
battery
REPLACE
BATTERY
Low
when
battery
is
charged
Open
when
battery
fails
self
‐
test
BATTERY
MISSING
Low
when
battery
is
present
Open
when
battery
is
missing
LOW
BATTERY
Low
when
battery
is
near
full
charge
capacity
Open
when
operating
from
a
battery
with
less
than
20%
capacity