Chapter 2. Installation
61202076L1-1
TSU 600 User Manual
2-3
Installing and Replacing the Power Supply
The following steps show how to install a new supply or replace a failed
supply.
Power does not have to be turned off on a working supply to add a new supply
or replace a failed one.
Step
Action
1
One Power Supply
If only one supply is installed in the chassis, remove the
blank panel covering the unused power supply slot.
Two Power Supplies
If two power supplies are installed, the failed supply can be
identified by the alarm on the front panel LCD. The alarm
message will identify a failure on Power Supply A or Power
Supply B. The option slot legend on the rear panel shows the
location of each power supply. Turn the power switch to Off
on the failed supply and unplug the power cord from the
power source.
2
Remove the two screws that secure the power supply mod-
ule to the TSU 600e chassis and remove the failed power sup-
ply module.
3
Remove the new power supply from the shipping con-
tainer. Make sure the power switch is in the
Off
position.
4
Plug the new supply into the open power supply slot and
install the two screws on the power supply module
5
Plug the new power supply cord into a grounded 115 VAC,
50/60 Hz power receptable.
6
Turn the power switch On.
Содержание 1202076L1
Страница 18: ...List of Figures vi TSU 600 User Manual 61202076L1 1...
Страница 20: ...List of Tables viii TSU 600 User Manual 61202076L1 1...
Страница 54: ...Chapter 3 Operation 3 14 TSU 600 User Manual 61202076L1 1...
Страница 76: ...Chapter 5 Configuration Menu 5 16 TSU 600 User Manual 61202076L1 1...
Страница 98: ...Chapter 8 Telnet Terminal Menus 8 10 TSU 600 User Manual 61202076L1 1...
Страница 106: ...Appendix B Understanding TR 08 B 4 TSU 600 User Manual 61202076L1 1...
Страница 116: ...Appendix E Specifications E 4 TSU 600 User Manual 61202076L1 1...