Chapter 2. Installation
61202052L1-1
TSU 100 User Manual
2-3
equipment grounding conductor shall be in compliance with
the rules for terminating bonding jumpers at Part K or Article
250 of the National Electrical Code, ANSI/NFPA 70. Termina-
tion of the supplementary equipment grounding conductor is
permitted to be made to building steel, to a metal electrical
raceway system, or to any grounded item that is permanently
and reliably connected to the electrical service equipment
ground.
Bare, covered, or insulated grounding conductors are accept-
able. A covered or insulated grounding conductor shall have a
continuous outer finish that is either green, or green with one
or more yellow stripes.
The supplemental grounding conductor shall be connected to
the equipment using a number 8 ring terminal. The terminal
should be fastened to the grounding lug provided on the rear
panel of the equipment. The ring terminal should be installed
using the appropriate crimping tool (AMP P/N 59250 T-EAD
Crimping Tool or equivalent).
Содержание 1202052L1
Страница 1: ...TSU 100 TSU 100e User Manual Part Numbers 1202052L1 1202052L2 January 1999 61202052L1 1C ...
Страница 18: ...List of Figures xviii TSU 100 User Manual 61202052L1 1 ...
Страница 20: ...List of Tables xx TSU 100 User Manual 61202052L1 1 ...
Страница 34: ...Chapter 2 Installation 2 10 TSU 100 User Manual 61202052L1 1 ...
Страница 48: ...Chapter 3 Operation 3 14 TSU 100 User Manual 61202052L1 1 ...
Страница 110: ...Appendix A Understanding SNMP A 6 TSU 100 User Manual 61202052L1 1 ...
Страница 114: ...Appendix B Understanding TR 08 B 4 TSU 100 User Manual 61202052L1 1 ...
Страница 120: ...Appendix C Network Pinouts C 6 TSU 100 User Manual 61202052L1 1 ...
Страница 126: ...Appendix E Specifications E 4 TSU 100 User Manual 61202052L1 1 ...
Страница 134: ...Index Index 8 TSU 100 User Manual 61202052L1 1 ...
Страница 136: ......