C A U T I O N
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
For more information, refer to the Installation and Maintenance Guide (P/N 61184561P4-5)
available online at
Warranty:
ADTRAN will replace or repair this product within the warranty period if it does not
meet its published specifications or fails while in service. Warranty information can
be found online at
©2010 ADTRAN, Inc. All Rights Reserved.
ADTRAN CUSTOMER CARE:
From within the U.S. 1.800.726.8663
From outside the U.S. +1 256.963.8716
PRICING AND AVAILABILITY 1.800.827.0807
*61184561P4-22C*
WARNING
!
The
Gigabit
Ethernet
port
is
classified
as
Type
2
or
Type
4,
as
defined
in
Appendix
B
of
GR
‐
1089
‐
CORE
Issue
4,
and
is
suitable
for
connection
to
intra
‐
building
or
unexposed
wiring
or
cabling
only.
Do
not
metallically
connect
this
port
to
interfaces
which
connect
to
the
Outside
Plant
(OSP)
or
to
the
OSP
wiring.
The
Gigabit
Ethernet
port
is
designed
for
use
as
an
intrabuilding
interface
only
(Type
2
or
Type
4
ports
as
described
in
GR
‐
1089
‐
CORE
Issue
4)
and
requires
isolation
from
exposed
OSP
cabling.
The
addition
of
Primary
Protectors
is
not
sufficient
protection
in
order
to
connect
this
interface
metallically
to
OSP
wiring.
The
Gigabit
Ethernet
port
is
suitable
for
connection
only
to
shielded
intra
‐
building
cabling
grounded
at
both
ends.
CAUTION
!
♦
Per
GR
‐
1089
‐
CORE
the
ADTRAN
system
that
the
SFP
is
being
deployed
in
is
designed
and
intended
for
installation
as
part
of
a
Common
Bonding
Network
(CBN).
The
ADTRAN
system
that
the
SFP
is
being
deployed
in
is
not
designed
nor
intended
for
installation
as
part
of
an
Isolated
Bonding
Network
(IBN).
♦
Per
GR
‐
1089
‐
CORE
Section
9,
the
SFPGC
does
not
have
an
internal
DC
connection
between
battery
return
and
frame
ground.
The
SFPGC
can
be
installed
in
a
DC
‐
I
(isolated)
or
DC
‐
C
(common)
installation.
For
installations
where
other
cards
or
the
host
system
have
internal
connections
between
battery
return
and
frame
ground,
the
system
would
be
intended
for
deployment
only
in
a
DC
‐
C
installation.
♦
The
ADTRAN
system
chassis
frame
ground
terminal
must
be
connected
to
an
earth
ground
to
ensure
that
the
metal
enclosure
of
the
SFPGC
is
properly
grounded
via
the
backplane
connector.
The
SFPGC
is
designed
to
meet
the
following
environmental
classes:
♦
ETSI
EN
300
019
‐
1
‐
1
“Classification
of
environmental
conditions;
Storage,”
Class
1.2
♦
ETSI
EN
300
019
‐
1
‐
2
“Classification
of
environmental
conditions,
Transportation,”
Class
2.3
♦
ETSI
EN
300
019
‐
1
‐
3
“Classification
of
environmental
conditions,
Stationary
use
at
weather
‐
protected
locations,”
Class
3.3
The
equipment
is
designed
to
function
without
degradation
during
exposure
to
all
test
severities
per
Class
3.3.