iQF-Series Modbus RTU Setup
2018/12/18
P a g e
|
10
CS80-VSD Setup
Recommended Parameter Settings
These are parameters used on the VSD and their settings:
Parameter 0 (Torque) = 10.
Parameter 1 (Max Frequency) = 50.
Parameter 2 (Min Frequency) = 20.
Parameter 3 (Base Frequency) = 50.
Parameter 4 (High Speed Set point) = 50.
Parameter 5 (Middle Speed Set point) = 35.
Parameter 6 (Low Speed Set point) = 20.
Parameter 7 (Acceleration Time) = 5.
Parameter 8 (Deceleration Time) = 5.
Parameter 9 (OL Relay) = 4.20.
Parameter 19 (Motor Name Plate Voltage) = 220.
Parameter 75 (Reset selection/disconnected PU detection/PU stop selection) = 14.
Parameter 77 (Parameter Write Selection) = 2.
Parameter 79 (Operation Mode Set) = 2.
Parameter 117 (PU Communication Station Number) = 1.
Parameter 118 (PU Communication Speed) = 192.
Parameter 119 (PU Communication Stop Bit Length / Data Length) = 0.
Parameter 120 (PU Communication Parity Check) = 2.
Parameter 121 (PU Communication Retry Count) = 1.
Parameter 122 (PU Communication Check Time Interval) = 5.
Parameter 124 (PU Communication CR/LF Selection) = 2.
Parameter 338 (Communication Operation Command Source) = 0.
Parameter 339 (Communication Speed Command Source) = 0.
Parameter 340 (Communication Start-up Mode Selection) = 1.
Parameter 549 (Protocol Selection) = 1.
Parameter 551 (PU mode operation command source selection) = 4.
Содержание Mitsubishi Electric IQF Series
Страница 1: ...iQF Series Modbus RTU Setup 2018 12 18 P a g e 1 IQF SERIES MODBUS RTU SETUP ...
Страница 8: ...iQF Series Modbus RTU Setup 2018 12 18 P a g e 8 Figure 7 ...
Страница 17: ...iQF Series Modbus RTU Setup 2018 12 18 P a g e 17 Figure 17 ...
Страница 18: ...iQF Series Modbus RTU Setup 2018 12 18 P a g e 18 Figure 18 ...