START-UP AND OPERATION 

 

Unit Start-Up 

 

FOR YOUR SAFETY READ BEFORE LIGHTING 

Electric shock hazard. Can cause

 

injury

or death. Do not use this heater if

 

any

part has been under water.

 

Immediately

call a qualified service technician to

 

in-

spect the furnace and to replace any

 

part

of the control system and any gas con-
trol which has been under water.

WARNING

!

 

Danger of explosion. Can cause injury or
product or property damage. If over-
heating occurs or if gas supply fails

 

to

shut off, shut off the manual gas valve

 

to

the appliance before shutting off

 

electri-

cal supply.

WARNING

!

 

Electric shock hazard. Can cause

 

injury or

death. Before attempting to

 

perform any

service or maintenance, turn the

 

electrical

power to unit OFF at disconnect

 

switch(es).

Unit may have multiple power supplies.

WARNING

!

 

Danger of explosion and fire. Can

 

cause

injury or product or property

 

damage.

 

You

must follow these instructions exactly.

WARNING

!

 

BEFORE LIGHTING smell all around the appliance area 
for gas. Be sure to smell next to the floor because some 
gas is heavier than air and will settle on the floor. 

 

Use only your hand to push in or turn the gas control 
knob. Never use tools. If the knob will not push in or turn 
by hand, do not try to repair it, call a qualified service 
technician. Force or attempted repair may result in a fire 
or explosion. 

 

These unit heaters are equipped with an automatic 
spark ignition system. There is no pilot. In  case of a 
safety shutdown, move thermostat switch to 

OFF

, then 

return the thermostat switch to 

HEAT

 position. 

 

Operation for Honeywell VR8205 Series Gas Valve 
(Figure 10) 

1- 

STOP!

 Read the safety information at the beginning 

of this section. 

2-  Set thermostat to lowest setting. 

 

HONEYWELL VR8205 SERIES GAS VALVE

GAS VALVE SHOWN IN OFF POSITION

MANI-
FOLD
PRESS-
URE
TAP

ON

OFF

FIGURE 10

MANIFOLD PRESSURE ADJUSTMENT SCREW

INLET
PRESSURE
TAP

 

3-  Turn off all electrical power to appliance. 

4- 

This appliance is equipped with an ignition device 
which automatically lights burners. 

DO

 

NOT attempt 

to light the burners manually. 

5-  Turn the manual knob on gas valve clockwise to 

OFF. 

Do not force. 

6-  Wait five (5) minutes to clear out any gas. If you 

then smell gas, 

STOP!

  Immediately call your 

gas supplier from a neighbor's phone. Follow the 
gas supplier's instructions. If you do not smell 
gas, go to next step. 

7-  Turn manual knob on gas valve counterclockwise to 

ON

8-  Turn on all electric power to unit. 
9-  Set thermostat to desired setting. 
10- The combustion air blower will start. The burners will 

light within 40 seconds. 

11- 11 If unit does not light first time (gas line not fully 

purged) it will attempt up to two more ignitions 
before locking out. 

12- If lockout occurs, repeat steps 1 through 9. 
13- If appliance still will not operate, follow the 

instructions “

To Turn Off Gas to Unit

" and call your 

service technician or gas supplier. 

Содержание FSAN Series

Страница 1: ...11 Requirements 2 Heating Sequence of Operation 13 Unit Heater Installation 3 Ignition Control LED 13 Combustion Ventilation Air 3 Adjustments 14 Venting 4 Service 15 Electrical Connections 9 Wiring Diagram 16 Gas Connection 10 Warranty 17 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE P N 065341302 ORGINATED 11 03 REVISED 05 08 SUPERSEDES 065341301 FSA N P ...

Страница 2: ... Furnace Btu Input _____________________________________________ Line Pressure_________________________________________________ Job No _________________________ City ____________________________ City ____________________________ Serial No ________________________ Date ____________________________________ State Province ____________________________ Service Technician _________________________ Flue ...

Страница 3: ... the regulations of the current National Electric Code ANSI NFPA No 70 The National Electric Code is available from National Fire Protection Association 1 Batterymarch Park PO Box 9101 Quincy MA 02269 9101 Requirements CSA in Canada The instructions are intended only as a general guide and do not supersede local codes in any way Authorities having jurisdiction should be consulted before installati...

Страница 4: ...cket to back of unit with screws provided in bag assembly containing flue transition 5 To support unit secure mounting bracket to ceiling joist or truss Unit may also hang on rods as shown in Figure 1 Combustion and Ventilation Air Adequate facilities for supplying air for combustion and ventilation must be provided in accordance with the latest edition of section 5 3 Air for Combustion and Ventil...

Страница 5: ...according to the section A General Recommendations and Requirements B Vertical Vents Using Metal Vent Pipe Commercial and Residential Installations These compact unit heaters are listed as Category I appliances for vertical vent installations 2 The vent connector shall be 3 76mm diameter on 30 45 units and 4 100mm diameter on 60 75 units In all cases a flue transition piece supplied is required to...

Страница 6: ...mum 6 ft 1 8mm horizontal clearance from gas and electric meters and relief devices as specified in the Canadian B149 1 Natural Gas Installation Code 5 Vent termination must be a minimum of 4 1 2m below or 4 1 2m horizontally from any soffit vent or under eave vent 6 Vent must be a minimum of 6 from an inside corner formed by two exterior walls If possible leave a 10 clearance 7 Vent termination m...

Страница 7: ... TERMINATION TEE 12 30 5CM MINIMUM ABOVE HIGHEST SNOWFALL DRAIN LOOP WITH WATER TRAP TO CONDENSATE DRAIN LISTED THIMBLE THROUGH COM BUSTIBLE WALL MAY BE SINGLE WALL 26 GSG GALV OR EQUIV STAINLESS STEEL SEALED ACCORDING TO THESE INSTALLATION INSTRUCTIONS SLOPE 1 4 INCH FOR 1 FOOT RUN MINIMUM 12 INCHES MIN 30 5 CM GROUND LEVEL UPWARD SLOPE ON HORIZONTAL VENT COMMERCIAL INSTALLATION NOTE MINIMUM HORI...

Страница 8: ...Residential Refer to Figure 6 2 The vent pipe diameter for horizontal residential installations shall be 4 100 mm on 30 45 units and 5 127 mm on 60 75units A standard vent transition is required at unit in addition to the transition supplied with the unit 3 The maximum vent length is 5 1 5 m plus one 90 degree elbow 4 The vent must maintain a rise per foot of slope upwards toward the termination 5...

Страница 9: ...annot be used as liners the chimney must be rebuilt to accommodate one of these methods or some alternate approved method must be found to vent the appliance When inspection reveals that an existing chimney is not safe for the intended purpose it shall be rebuilt to conform to nationally recognized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable f...

Страница 10: ...eaters to a microprocessor controlled thermostat Install the thermostat according to instructions provided Select circuit protection and wire size according to the unit rating plate Install a separate disconnect switch protected by either fuse or circuit breaker near the unit so that power can be turned off for servicing Connect wiring through knockout on the junction box located on the side of th...

Страница 11: ...upply connection to the heater NOTE Compounds used on threaded joints of gas piping must be resistant to the actions of liquefied petroleum gases FIGURE 8 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Furnished by Installer GAS FLOW 1 8 NPT PLUGGED TAP GAS SUPPLY CONNECTION Leak Check After gas piping is completed carefully check all piping connections field and factory for gas leaks Use ...

Страница 12: ...e or explosion These unit heaters are equipped with an automatic spark ignition system There is no pilot In case of a safety shutdown move thermostat switch to OFF then return the thermostat switch to HEAT position Operation for Honeywell VR8205 Series Gas Valve Figure 10 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest setting HONEYWELL VR8205 SERIES ...

Страница 13: ... the instructions To Turn Off Gas to Unit and call your service technician or gas supplier Gas Valve Operation for Robertshaw 2000DER Series Valve Figure 12 5 STOP Read the safety information at the beginning of this section 6 Set the thermostat to lowest setting 7 Turn off all electrical power to appliance 8 This appliance is equipped with an ignition device which automatically lights burner DO N...

Страница 14: ...e lifting from the burner heads flashback or burning within the burner The flames shall be predominantly blue in color and shall be approximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the fan approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed 5 seconds after the dem...

Страница 15: ...o convert unit Refer to installation instructions provided with changeover kit for conversion procedure Limit Control The limit control switch is factory set and not field adjustable Louver Vane Adjustment Rotate louver vanes to direct airflow upward downward straight or any combination of these directions When unit is installed in an inverted position louvers may be positioned in the same manner ...

Страница 16: ...ews securing flue box to unit Remove flue box If necessary remove blower assembly from flue box Clean flue box with wire brush 4 Remove turbulator retention bracket and turbulators Clean turbulators with wire brush 5 Remove burners as described in section Burners section 6 Clean tubes with a wire brush 7 Reassemble unit The combustion air and flue box gaskets should also be replaced during reassem...

Страница 17: ...1 2 S47 SWITCH FLAME ROLLOUT 2 S43 SWITCH LOW GAS PRESSURE T1 TRANFORMER CONTROL WIRING DIAGRAM 3 01 HEATING UNITS GAS DSI LF24 30 45 60 75 FSAN P 30 45 60 75 CGHA DUHA 030 045 060 075 SUPERSEDES FORM NO NEW FORM NO 065277500 MAXIMUM LOAD NOT TO EXCEED 20 VA AT 24 V CLASS 2 2 S47 USED ON THE 60 75 MODELS ONLY DISCONNECT ALL POWER BEFORE SERVICING FOR PROPER GROUNDING REFER TO LOCAL CODES WIRING SC...

Страница 18: ... operated and maintained in accordance with the installation operation and maintenance instructions provided with each unit Unauthorized alteration of ADP product may void this warranty Conditions of Warranty Replacement parts furnished under this warranty will be warranted for the balance of the original warranty term of the unit including any extended warranty and will not serve to extend the or...

Отзывы: