Adp FSAN Series Скачать руководство пользователя страница 3

 

Page 2 

 

Shipping 

 

The heater is completely assembled. Installation 
instructions, two mounting brackets (shipped loose), and 
a flue transition are included. Check the unit for shipping 
damage. The receiving party should contact the last 
carrier immediately if any shipping damage is found. 

 

Requirements – CSA in the USA 

 

Installation of gas unit heaters must conform with local 
building codes or, in the absence of local codes, with the 
current National Fuel Gas Code ANSI Z223.1. 
Installation in aircraft hangers must be in accordance with 
the current Standard for Aircraft Hangers ANSI/NFPA No. 
409. 
Installation in parking structures must be in accordance 
with the current Standard for Parking Structures 
ANSI/NFPA No. 88A. 
Installation in repair garages must be in accordance with 
the current Standard for Repair Garages ANSI/NFPA No. 
88B. 
These units are approved for residential applications. For 
installation in a residential garage these units must  be 
installed so that burners and ignition source are located 
no less than 18" (457mm) above floor. Heater must be 
located or protected to avoid physical damage by 
vehicles. Refer to the National Fuel Gas Code, ANSI 
Z223.1, current edition. 
Authorities having jurisdiction should be consulted before 
installation. Air for combustion and ventilation must 
conform to the methods outlined in ANSI Z223.1, section 
5.3, Air for Combustion and Ventilation, or applicable 
provisions of local building codes. 
The National Fuel Gas Code is available from: 
 

American National Standard Institute Inc. 

 

11 West 42nd Street 

 

New York, NY 10036 

These units are CSA International design certified. These 
unit heaters are certified for installation to combustible 
material as listed in Table 1 and on unit rating plate. 
Accessibility and service clearances must be observed in 
addition to fire protection clearances. 
All electrical wiring and ground for unit must be in 
accordance with the regulations of the current National 
Electric Code ANSI/NFPA No. 70. 

The National Electric Code is available from: 
 

National Fire Protection Association 

 

1 Batterymarch Park 

 

PO Box 9101 

 

Quincy, MA 02269-9101 

 

Requirements – CSA in Canada 

 

The instructions are intended only as a general guide and 
do not supersede local codes in any way. Authorities 
having jurisdiction should be consulted before installation. 
The installation must conform with local building codes or 
in the absence of local codes, with the current code 
CAN/CGA-B149.1 “Installation Code for  Natural Gas 
Burning Appliances and Equipment." All electrical wiring 
and grounding for the unit must also comply with the 
Canadian Electrical Code CSA C22.1, current edition. 

These unit heaters are CSA International. Certified for the 
clearances to combustible material listed on the rating 
plate and Table 1. Adequate clearance shall be provided 
around the appliance and around air openings into the 
combustion chamber. Provision shall be made for service 
accessibility to the heater. Note that fire protection 
clearances may be exceeded to provide additional space 
for service and accessibility. 

GARAGE INSTALLATIONS: 

1-  In a storage area, clearance from heaters to 

combustible materials must be such that the material 
shall not attain a temperature above 160°F by 
continuous operation of the unit. 

2-  Eight-foot minimum clearance from the floor to the 

bottom of the heater must be maintained. Refer to the 
CAN/CGA-B149 Codes. 

AIRCRAFT HANGER: 

1-  In an area where aircraft are housed or serviced, 10' 

minimum clearance from highest surface of aircraft to 
bottom of the heater must be maintained. 

2-  In other areas, 8' minimum clearance from the floor to 

bottom of heater must be maintained. 

3-  Heaters should be located so as to be protected from 

damage from aircraft or other appliances needed for 
servicing of aircraft Refer to requirements of the 
enforcing authorities. 

TABLE 1 

UNIT CLEARANCES 

Top 

Sides 

Access Panel 

Bottom 

Rear 

Single Wall Vent* 

in 

mm 

in 

mm 

in 

mm 

in 

mm 

in 

mm 

in 

mm 

25 

25 

18 

457 

18 

457 

152 

      *Except for listed clearance thimbles.

Содержание FSAN Series

Страница 1: ...11 Requirements 2 Heating Sequence of Operation 13 Unit Heater Installation 3 Ignition Control LED 13 Combustion Ventilation Air 3 Adjustments 14 Venting 4 Service 15 Electrical Connections 9 Wiring Diagram 16 Gas Connection 10 Warranty 17 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE P N 065341302 ORGINATED 11 03 REVISED 05 08 SUPERSEDES 065341301 FSA N P ...

Страница 2: ... Furnace Btu Input _____________________________________________ Line Pressure_________________________________________________ Job No _________________________ City ____________________________ City ____________________________ Serial No ________________________ Date ____________________________________ State Province ____________________________ Service Technician _________________________ Flue ...

Страница 3: ... the regulations of the current National Electric Code ANSI NFPA No 70 The National Electric Code is available from National Fire Protection Association 1 Batterymarch Park PO Box 9101 Quincy MA 02269 9101 Requirements CSA in Canada The instructions are intended only as a general guide and do not supersede local codes in any way Authorities having jurisdiction should be consulted before installati...

Страница 4: ...cket to back of unit with screws provided in bag assembly containing flue transition 5 To support unit secure mounting bracket to ceiling joist or truss Unit may also hang on rods as shown in Figure 1 Combustion and Ventilation Air Adequate facilities for supplying air for combustion and ventilation must be provided in accordance with the latest edition of section 5 3 Air for Combustion and Ventil...

Страница 5: ...according to the section A General Recommendations and Requirements B Vertical Vents Using Metal Vent Pipe Commercial and Residential Installations These compact unit heaters are listed as Category I appliances for vertical vent installations 2 The vent connector shall be 3 76mm diameter on 30 45 units and 4 100mm diameter on 60 75 units In all cases a flue transition piece supplied is required to...

Страница 6: ...mum 6 ft 1 8mm horizontal clearance from gas and electric meters and relief devices as specified in the Canadian B149 1 Natural Gas Installation Code 5 Vent termination must be a minimum of 4 1 2m below or 4 1 2m horizontally from any soffit vent or under eave vent 6 Vent must be a minimum of 6 from an inside corner formed by two exterior walls If possible leave a 10 clearance 7 Vent termination m...

Страница 7: ... TERMINATION TEE 12 30 5CM MINIMUM ABOVE HIGHEST SNOWFALL DRAIN LOOP WITH WATER TRAP TO CONDENSATE DRAIN LISTED THIMBLE THROUGH COM BUSTIBLE WALL MAY BE SINGLE WALL 26 GSG GALV OR EQUIV STAINLESS STEEL SEALED ACCORDING TO THESE INSTALLATION INSTRUCTIONS SLOPE 1 4 INCH FOR 1 FOOT RUN MINIMUM 12 INCHES MIN 30 5 CM GROUND LEVEL UPWARD SLOPE ON HORIZONTAL VENT COMMERCIAL INSTALLATION NOTE MINIMUM HORI...

Страница 8: ...Residential Refer to Figure 6 2 The vent pipe diameter for horizontal residential installations shall be 4 100 mm on 30 45 units and 5 127 mm on 60 75units A standard vent transition is required at unit in addition to the transition supplied with the unit 3 The maximum vent length is 5 1 5 m plus one 90 degree elbow 4 The vent must maintain a rise per foot of slope upwards toward the termination 5...

Страница 9: ...annot be used as liners the chimney must be rebuilt to accommodate one of these methods or some alternate approved method must be found to vent the appliance When inspection reveals that an existing chimney is not safe for the intended purpose it shall be rebuilt to conform to nationally recognized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable f...

Страница 10: ...eaters to a microprocessor controlled thermostat Install the thermostat according to instructions provided Select circuit protection and wire size according to the unit rating plate Install a separate disconnect switch protected by either fuse or circuit breaker near the unit so that power can be turned off for servicing Connect wiring through knockout on the junction box located on the side of th...

Страница 11: ...upply connection to the heater NOTE Compounds used on threaded joints of gas piping must be resistant to the actions of liquefied petroleum gases FIGURE 8 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Furnished by Installer GAS FLOW 1 8 NPT PLUGGED TAP GAS SUPPLY CONNECTION Leak Check After gas piping is completed carefully check all piping connections field and factory for gas leaks Use ...

Страница 12: ...e or explosion These unit heaters are equipped with an automatic spark ignition system There is no pilot In case of a safety shutdown move thermostat switch to OFF then return the thermostat switch to HEAT position Operation for Honeywell VR8205 Series Gas Valve Figure 10 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest setting HONEYWELL VR8205 SERIES ...

Страница 13: ... the instructions To Turn Off Gas to Unit and call your service technician or gas supplier Gas Valve Operation for Robertshaw 2000DER Series Valve Figure 12 5 STOP Read the safety information at the beginning of this section 6 Set the thermostat to lowest setting 7 Turn off all electrical power to appliance 8 This appliance is equipped with an ignition device which automatically lights burner DO N...

Страница 14: ...e lifting from the burner heads flashback or burning within the burner The flames shall be predominantly blue in color and shall be approximately centered in the tubes with no apparent impingement taking place 7 The ignition control will energize the fan approximately 45 seconds after ignition is established 8 After the thermostat demand is satisfied the gas valve is closed 5 seconds after the dem...

Страница 15: ...o convert unit Refer to installation instructions provided with changeover kit for conversion procedure Limit Control The limit control switch is factory set and not field adjustable Louver Vane Adjustment Rotate louver vanes to direct airflow upward downward straight or any combination of these directions When unit is installed in an inverted position louvers may be positioned in the same manner ...

Страница 16: ...ews securing flue box to unit Remove flue box If necessary remove blower assembly from flue box Clean flue box with wire brush 4 Remove turbulator retention bracket and turbulators Clean turbulators with wire brush 5 Remove burners as described in section Burners section 6 Clean tubes with a wire brush 7 Reassemble unit The combustion air and flue box gaskets should also be replaced during reassem...

Страница 17: ...1 2 S47 SWITCH FLAME ROLLOUT 2 S43 SWITCH LOW GAS PRESSURE T1 TRANFORMER CONTROL WIRING DIAGRAM 3 01 HEATING UNITS GAS DSI LF24 30 45 60 75 FSAN P 30 45 60 75 CGHA DUHA 030 045 060 075 SUPERSEDES FORM NO NEW FORM NO 065277500 MAXIMUM LOAD NOT TO EXCEED 20 VA AT 24 V CLASS 2 2 S47 USED ON THE 60 75 MODELS ONLY DISCONNECT ALL POWER BEFORE SERVICING FOR PROPER GROUNDING REFER TO LOCAL CODES WIRING SC...

Страница 18: ... operated and maintained in accordance with the installation operation and maintenance instructions provided with each unit Unauthorized alteration of ADP product may void this warranty Conditions of Warranty Replacement parts furnished under this warranty will be warranted for the balance of the original warranty term of the unit including any extended warranty and will not serve to extend the or...

Отзывы: