Command Set 3-17
The command sets the analog output to be 16 mA at address 06H, if
the data format is configured as engineering units and 0~20mA output
range.
User command:
#08+020.00<CR>
Response:
><CR>
The command sets the analog output to be 4 mA at address 08H, if
the data format is configured as % of FSR and 0~20mA output range.
4mA = 20mA x 20.00%
User command:
#097FF<CR>
Response:
><CR>
The command sets the analog output to be 5 V at address 09H, if the
data format is configured as hexdecimal format and output range of
0~10V.
5 V = 7FF / FFF x 10V
User command:
#08A-05.000<CR>
Response:
><CR>
The command sets the analog output port A to be –5 V at address
08H.
Содержание ND-6021
Страница 1: ...ND 6021 ND 6024 Analog Input Modules User s Guide...
Страница 14: ......
Страница 20: ......
Страница 54: ......