Vcc is a direct voltage (between 7
and 30VDC) supplied by the user.
The value of the resistance
R
depends on the customer
installation.
B 40
Remote control connector wiring
Wiring of the remote
S1, 53, 54 and 55 are inputs.
control plug
S2 is an output (open collector)
Do not add any strap except Si, 53, S4 and S5.
Output S2:
Do not connect a relay between the pins 5 and 6.
The relay coil induces a current which may result in damage of the
frequency converter unit.
Wiring of output 52:
The maximum value of the current in the output must be of 35 mA.
51:
start/stop
52 closed:
pump at speed
53, 54, 55:
rotational speed selection
Pin 8, 10, 12 and 14 are
connected to the ground of the
control unit.
Wiring of output S2
S2 is an open collector output and must be wired as shown below.
2/3