General
B 30
Electrical connections
The performance and the operational safety of this product is
guaranteed provided that it is used in normal operating parameters
defined in this manual.
Any modification of the pump not improved by the manufacturer
can compromise the protection ensured by the pump.
Our products are designed to comply with current EC regulations.
Any modification of the product made by the user is liable to lead
to non-compliance with these regulations, or to reduce the EMC
(ElectroMagnetic Compatibility) performance and the safety of the
product. The manufacturer declines any responsability for such
operations.
The EMC performance of the product is obtained on the condition that
the installation complies with the EMC rules. In particular, in disturbed
environments, it is essential to:
- use shielded cables and connections for interfaces,
- stabilize the power supply line with meshing from the power supply
source to a distance of 3m (10 ft) from the pump inlet.
Lock out/tag out (LO/TO) electrical device.
In order to properly secure the pump for installation and/or
maintenance, it is required to lock out/tag out the pump properly in
accordance with OSHA requirement 29 CFR.1910.147.
When switching off an item of equipment containing capacitors loaded
at over 60 VDC or 25 VAC, take precautions concerning the access to the
connector pins (single-phase motors, fitting with line filter, frequency
converter, monitoring system, etc.).
Operation in local mode
There is no device to warn that the pump operates in local mode.
When the pump is not integrated in the equipment/host tool, the user
must provide a device to warn that the pump operates in local mode.
The pump is not equipped with a 10000 AIC main breaker. Electrical
shock may result in severe injury.
Power the pump from a facilities supplied 15 A mini main circuit breaker
with a 10000 AIC rating.
The user supplied certified branch fuse should be in close proximity to
the pump (no further than 7m (25 ft) within line of sight of the pump).
Alcatel Vacuum Technology France - Manuel de l'Utilisateur - ACP 15 / 28 / 40 Series 2
1/2
Содержание ACP 15
Страница 1: ......
Страница 12: ...Dimensional drawing mm inch ...
Страница 16: ...Dimensional drawing mm inch ...
Страница 21: ...B 00 Safety instructions Alcatel Vacuum Technology France Manuel de l Utilisateur ACP 15 28 40 Series 2 1 5 ...
Страница 45: ...G10 ACP 15 15 G pumping curves ...
Страница 46: ...G11 ACP 28 28 G pumping curves ...
Страница 47: ...G12 ACP 40 40 G pumping curves ...
Страница 49: ...G 101 52 SEMI Certificate 1 1 Alcatel Vacuum Technology France Manuel de l Utilisateur ACP 15 28 40 Series 2 ...