ADI LT boiler – Technical manual
Page
37
15.7.3 Hydraulic pressure drop
The boiler pressure drop depends on the water flow; the maximum
∆
T must be 15 ºC:
ADI LT
Units
120
150
180
220
270
330
400
500
Flow rate
∆
T = 7ºC
m
3
/h
14,4
18,6
21,8
27,0
32,0
39,6
46,9
57,1
Flow rate
∆
T = 10ºC m3/h
10,1
13,0
15,2
18,9
22,4
27,7
32,9
40,0
Flow rate
∆
T = 12ºC
m
3
/h
8,4
10,8
12,7
15,8
18,6
23,1
27,4
33,3
If you have to stop the boiler pump, it is required that you stop it with a time delay (3 to 5 minutes) once the
boiler has stopped. This can be obtained by installing a timer-disconnect electrical relay.
0,30
0,80
1,30
1,80
2,30
2,80
7
17
27
37
47
57
Caudal (m
3
/h)
P
é
rd
id
a
(
m
.c
.a
.)