8.5.4
Update unit data
If the ADICOS central software is used permanently for monitoring measurement data, an
update of the device data at the ADICOS central software is mandatory.
An update of the device data on the ADICOS central software has no effect on
the functionality of the new device.
Call up the unit for updating
1
Open ADICOS central software
2
Call up “Service Funktoinen”
3
Select the button “Unit input”. (De
-
vice input) button
4
Select the old unit in the “Aktive
Geräte” table by double-clicking on
it
Z
„GSME-Dateneingabe“ window is
open
5
Read in the serial number of the new
device by pressing the “Von Melder lesen” button. Then confirm with “OK”
8.5.5
Optimise alarm thresholds (optional)
Even with a transfer of alarm thresholds from an old unit to a new unit, their
performance may differ.
Possible reasons for different performance with identical alarm thresholds are:
–
marginally varying cross-sensitivities
–
Contamination of the sintered metal filter of old units whose influence on the measure
-
ment result cannot be ompensated.
►
Optimise alarm thresholds or set new alarm thresholds using the following methods:
–
Long-term recording
Long-term recordings are used to record the usual fire gas concentrations at the site of
operation.
–
Fire test
Fire tests are used to determine the expected fire gas concentration in the event of an
alarm.