DTU2xx Data Logger Series 

User Guide. r. 2.1 | 2021-11-10 

 

 

Tel.:  +420 538 890 720 

27 

    e-mail: [email protected] 

Parameter

 

Description

 

Default value

 

Value options

 

Network registration 

standby time 

Maximum time to register in a network 

using both SIM cards 

(in case both cards are installed). If communica-

tion session fails, the next attempt to register in 

the network will occur after 1 hour, then after 2, 4, 

8, 24 hours, and then every 24 hours 

120 seconds

 

(if both cards are 

 inserted,  

60 seconds each) 

 

60 – 600  

seconds 

Frequency of  

sensors reading 

Setting inputs polling frequency 

2Hz

 

2 Hz/20 Hz/100 Hz 

Debug level 

When "AT-commands " mode is selected, "Debug 

Console" window shows a log of AT-commands 

displaying device status 

Disabled

 

Disabled/AT commands 

SIM card (1, 2) 

SIM card PIN code 

Required to enter, if a SIM card is used  

with the PIN code enabled. 

If the system PIN is enabled,  

the parameter is not filled in! 

not set

 

4 characters 

Use system  

PIN code 

System PIN automatic generation 

to prevent SIM card use in other devices 

Disabled

 

included/disabled 

Operator  

for NB-IoT data loggers only

 

Public Land Mobile Network (PLMN).  

Specified by the network operator 

00000

 

Set by the telecom opera-

tor 

GPRS user name 

Specified by the network operator 

Not set

 

1 – 31 characters 

GPRS password 

APN GPRS  

access point 

Specified by the network operator 

Not set

 

1 –  31 characters 

Enable SIM card  

activity control 

The option works only, if in the Active SIM 

card selection parameter Auto is set.

 

Enabling the option to monitor modem 

activity on SIM cards. 

On an inactive SIM, a periodic connection to 

the server will be initiated in order to prevent 
SIM card disconnecting for non-use. DTU will 

establish the connection from this card after 

the end of the period specified in the  

Maximum SIM card inactivity period line

If the device does not establish the connection 

after the end of the period specified in the 

Maximum SIM card inactivity period

, the 

event "The period of no connection on SIMx 

exceeded" will be generated, and then device 

will repeat connection attempts in accordance 
with the parameter 

Number of repeated con-

nections after inactivity

 

Disabled

 

Enable/ 

Disable 

Maximum SIM card 

inactivity period 

Number of days, when the data logger is allowed 

not to perform the SIM card activity control 

60

 

10 – 365 days 

Number of repeated 

connections after 

 inactivity 

Number of attempts to check the activity of an in-
active SIM card after the maximum period of inac-

tivity has expired 

1

 

1 – 10 

Server settings 

Server address 

IP address or server domain name, where the DTU 

is connecting to transmit data. 

iot24.eu: 

iot24.eu (TCP) 

139.162.147.141 

 (NB-IoT)

 

1  – 31 characters 

Содержание DTU2 Series

Страница 1: ...GPRS NB IoT Data Loggers DTU2xx User Guide Revision 2 1 November 2021...

Страница 2: ...ct may cause radio interference In such cases users may be required to take adequate measures WARNINGS Do not dispose electronic equipment as unsorted municipal waste Please use a separate collection...

Страница 3: ...gorithm of data logger communication 17 SIM card operation 17 Operating in NB IoT network 17 Backup battery power supply 18 2 Getting Started 19 Important safety information 19 Installing DTU data log...

Страница 4: ...n of the data logger in the event of external power failure Battery service life ranges from 4 to 10 years depending on the model GPRS or NB IoT and its use The model range of DTU2xx is represented by...

Страница 5: ...ounting Example of a modification name DTU227 UCG ZR Within each group of options the letters go alphabetically If the letters of the option group are not present in the modification name then the let...

Страница 6: ...NB IoT Cat NB2 Data transmission rate up to 85 6 kbps DL UL 125 kbps DL 150 kbps UL Protocol Stacks IPv4 TCP IPv4 TCP IPv4 UDP IPv4 TCP IPv4 UDP GPIO PARAMETERS Universal pulse inputs x4 IO1 IO4 Conne...

Страница 7: ...V DISABLED by default Enabled when the Current loop input is activated SIM 2 x mini SIM 2FF Antenna 1 x SMA F connector DEFAULT SETTINGS Data slice saving once per hour Readings transfer to server onc...

Страница 8: ...for connecting to the server configuring data logger 4 1 SIM 1 SIM card 1 holder 4 2 Button to remove SIM card 1 5 1 SIM 2 SIM card 2 holder 5 2 Button to remove SIM card 2 6 ANT SMA F connector for...

Страница 9: ...OUT G Ground 3 6V 3 6 V power output 3 6V 3 6 V power output 12 XP58 connector 5V 5 V power output 7 5V 7 5 V power output 12V 12 V power output 13 1 XP69 connector 7 30 VDC DTU217 DTU227 G Ground V...

Страница 10: ...when connecting high frequency impulse meters to the data logger Connection An example of a possible connection of meters to the data logger is given in figure below One wire of the meter is connecte...

Страница 11: ...ger Connection The sensor has a two wire connection scheme one wire is connected to any of the IO1 IO4 contacts and the other to the 3 6V contact Connection polarity is not important The plate is plac...

Страница 12: ...nsor receives power from the data line in parasitic mode Current Sensor 4 20 ma the type of input used when connecting 4 20mA current sensors to the data logger When this type is selected a 100 Ohm lo...

Страница 13: ...s where there is no external power supply at the facility since the device can operate autonomously from a 3500 mAh battery The interfaces are co located so all information received over a transparent...

Страница 14: ...the two channel mode On the one hand the data transfer channel from the GPIO ports via the ADGT DTU protocol is kept active and at the same time a separate transparent communication channel between RS...

Страница 15: ...nt mode and independently establishes an outgoing connection with the Server to which it sends data after the connection The default Server is the online dispatching server https iot24 eu The server i...

Страница 16: ...Condition Description External power connection ST1 reading is ON External power supply 12V or 230V connected ST1 reading is OFF External power is not connected Switching the device to configuration c...

Страница 17: ...minutes ahead of the specified hour The delay has a fixed value which is calculated based on the IMEI number of the connected DTU and can range from 0 to 60 minutes but not more than 60 min SIM card o...

Страница 18: ...n power supply unit depending on the model see Product Description Therefore the devices can be powered both from an external 7 30 VDC source and from the 100 240 VAC network through a two contact ter...

Страница 19: ...device does not have its own power switch and can be installed into hard to reach places electrical cabinets etc for safety reasons equip the device with an external power off switch The switch should...

Страница 20: ...or LTE NB IoT SMA m antenna to the ANT SMA f connector 4 Connect meters and sensors to the corresponding DTU GPIO connectors IO1 IO4 For pinouts see section Appearance Recommended wiring diagrams are...

Страница 21: ...Please observe the correct polarity G Ground negative input V 7 30 VDC positive input The maximum operating voltage input must not exceed 30V DC Reverse polarity will not cause damage but the data lo...

Страница 22: ...te after connecting the power this time is required to configure the inputs and establish a connection press the SB button to transmit the readings to https iot24 eu server Remember or write down the...

Страница 23: ...ion for Windows 32 bit 64 bit and Linux 64 bit versions at https adgt cz ATTENTION The DTU Configuration Tool program is written in Java therefore to start it you need to have Java Runtime Environment...

Страница 24: ...ade The button should be pressed after each change of the parameters Service functions Button opens the window where it is possible to update the firmware version reboot the device reset the DTU confi...

Страница 25: ...eration time time period of the device power supply operation starting from the device switch on and to the current moment The parameter is non resettable GSM connection GSM module status Enabled Disa...

Страница 26: ...ansmission Disables data transmission initiated by the Data Logger The data archive is transmitted only on request from the server Sporadic data transmission enabled Enabled Disabled Inputs trigger le...

Страница 27: ...operator Not set 1 31 characters GPRS password APN GPRS access point Specified by the network operator Not set 1 31 characters Enable SIM card activity control The option works only if in the Active...

Страница 28: ...the parameters do not forget to click the Write settings button Unsaved changes will be highlighted in yellow Configuring Inputs Each input parameters configuration could be performed at the Inputs t...

Страница 29: ...from the measur ing device non setting parameter Read from the meter Closed Opened Open short circuit Emergency discharge value Maximum pulse repetition rate at the input for 10 minutes When the pre e...

Страница 30: ...Parameter Description Default Value options Serial port parameters Serial baudrate Serial port speed of the connected meter 19200 bit s from 600 to 115200 bits c Parity and length Parity check mode a...

Страница 31: ...cond Allowable channel silence The parameter is only active when the device is powered by an ER18505 battery If there is silence in the channel during data transfer data is no longer transmitted the d...

Страница 32: ...y of a few minutes in advance from the specified hour DTU supports three types of schedule daily weekly and monthly The schedule configuration is performed at the Schedule tab using the following algo...

Страница 33: ...ters should be additionally set in case of possible connection problems Repeat if transmission failed the maximum number of attempts to transmit data on the day of the DTU connection to the Cloud Serv...

Страница 34: ...o read and to send meter readings SMS for example to the housing and utility services or to the management company The parameter is directly connected with the Number of days for repeated transmission...

Страница 35: ...To do this check the box in the appropriate field 2 If any of the data logger inputs operates in the Current loop mode and power is supplied to it from the 7 5V and 12V data logger outputs you need t...

Страница 36: ...of the week Days of week day of the month Day of month or the time period Period in which the device should communicate d In the Transmission hour line specify the time of communication on the specifi...

Страница 37: ...ut two minutes after that the device stays in the active mode for 15 minutes more and then passes to the sleep mode DTU Data Logger reset back to default settings is executed using the DTU Configurati...

Страница 38: ...DTU2xx Data Logger Series User Guide r 2 1 2021 11 10 Tel 420 538 890 720 38 e mail info adgt cz Fig 33 Updating the firmware of the DTU2xx data logger...

Страница 39: ...11 10 Tel 420 538 890 720 39 e mail info adgt cz Application 1 When using a DTU2xx C data logger with 230 VAC power supply for double protection against electric shock use the diagram below Fig 34 Do...

Отзывы: