Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
EnOcean / BACnet Slave
Document code: MN67C56_ENG Revision 1.000 Page 18 of 30
SET COMMUNICATION:
By Pressing the “
Set Communication
” button from the main window for SW67C56 (Fig. 2)
the window “Set Communication” appears (Fig. 3).
In the section “BACnet Slave” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter is
defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the converter is
defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This feature
can be enabled or disabled pressing the Check Box field. This feature is used for going
out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The default
port used for BACnet communication is 47808, but is possible to insert any value;
In the field "
BACnet Device Name
" the name of BACnet/IP side of the converter is
defined;
In the field “
Device Identifier
” the ID of BACnet/IP side of the converter is defined;
If the field “
BACnet description up to 32 chars
” is checked, the description of the
BACnet objects can be up to 32 chars.
Figure 3a: “Set Communication” window