Adey CP1-03-04913 Скачать руководство пользователя страница 14

26 

-

-

 27

 -

8 MAINTENANCE

8 .11 

Routine maintenance & service checks:

 

Every 6 & 12 months (see service log sheets below) the APU should be  

 

 

 

inspected for:-

 

z

Damage to the electrical supply cable .

 

z

Damage to the inlet and outlet flexible hoses .

 

z

Leakage from the APU or the connecting pipework .

 

z

Controller log check; fault codes, pump run times, etc .

 

z

Test unit operation 

 

z

Float valve check 

 

z

Level probe check

 

z

Water condition check

 

z

Expansion vessel pre-charge check

8 .12 

Wiring diagram

 

There are no user servicable wiring or components inside the controller    

 

 assembly . 

DO NOT remove the retaining screws or the membrane cover over  

 

 

the display .

8 .13 

Spares

 

The APU Midi is designed and built to be a reliable and high quality product,  

 

 

in the event of spares being required, please contact the ADEY Customer Services    

 

team on +44 (0) 1242 546 717 .

8 .14 

Long term isolation and restart procedure

 

If the system is to be shut down for an extended period of time due to  

 

 

 

maintainance or system modifications being carried out to the system the   

 

 

following steps must be taken .

1 .  Isolate mains inlet water from the APU Midi .

2 .  Isolate the APU Midi from the system and vent excess pressure to drain .

3 .  Run the APU to pump excess water from the tank to drain .

4 .  Isolate the electrical supply from the APU .

5 .  Remove the vent screws on  the front of the pumps and allow excess    

 

 

water to drain . Replace vent screws . See section 6 .26 .

6 . 

Ensure the pressurisation unit cannot freeze . Damage will occur to the pumps   

if this is allowed to happen .

7 .  Cover with plastic sheet or cardboard if work is to be conducted close to  

 

 

the APU .

8 .15 

Restart

 

To ensure the APU is in good working order after a prolonged period of  

 

 

 

maintainance the following steps should be taken .

1 .  Inspect the APU for signs of damage .

2 .  Check APU tank for debris, remove debris and clean tank if needed . Debris  

 

 

may cause damage to the pumps if it is allowed to be drawn in .

3 .  Check pressure vessel pre charge pressures before the system pressure is  

 

 increased . 

4 .  Open the mains water isolating valve allowing the APU tank to fill, and    

 

 

ensure the fill valve is operating correctly and maintaining the correct    

 

 

water level .

5 .  Check for signs of leakage .

6 .  Open the drain valve on the outlet of the APU .

7 .  Turn on the mains electrical power and ensure both (if fitted) pumps can  

 

 

run (use test pump option if needed) and are pumping water to drain .

8 .  Close the drain valve and allow the APU to build pressure; the pressurisation unit  

 

should turn off as the isolation valve to the system is closed .

9 .  Open the APU outlet isolation valve and monitor the APU to ensure there are  

 

 

no leaks as the system pressure increases . 

10 .  Check all the pre set values on the APU to ensure they are still suitable for  

 

 

the system (after maintainance/modification)

9  ENVIRONMENT PROTECTION

Your appliance contains valuable materials which can be recovered or recycled .

At the end of the product’s useful life, please leave it at an appropriate local civic waste 

collection point .

230 VAC/1PH/50Hz
SUPPLY

N
E

L

MAIN WINDING

THERMOTRIP

START WINDING

BLUE

BROWN

MOTOR 2

THERMOTRIP

BLUE

BROWN

MOTOR 1

PRESSURE TRANSDUCER
4-20mA, 0 - 10 bar

COMMON

LOW LEVEL

HIGH LEVEL

GREEN/YELLOW

GREEN/YELLOW

L  E  N

L  E  N

VO

LT

 F

RE

AL

AR

CO

NT

AC

TS

 - 

AM

MA

X.

RS 485 modbus

LOW PRESSURE ALARM N/O

HIGH PRESSURE ALARM N/O

BOILER INTERLOCK N/O

COMMON ALARM N/O

GREEN/YELLOW

BLUE

BROWN

RED

GR

EE

N

BLUE

C  L1  L2

- +

CAPACITOR

BLA

CK

BLU

E

MAIN WINDING

START WINDING

CAPACITOR

BL

AC

K

BLUE

2

1

BR

OWN

BLUE

TANK

1

2

3

4

Fig. 25

Содержание CP1-03-04913

Страница 1: ...Installation and servicing Midi 135 150 235 250 Digital Pressurisation Unit...

Страница 2: ...rated with the front cover in place z In the interests of electrical safety a 30 mA residual current device R C D not supplied should be installed in the supply circuit This may be part of a consumer...

Страница 3: ...l cause leakage 1 16 Secure pipework Ensure pipework to and from pump is independently supported clipped to prevent forces being transferred to inlet and outlet branches of the unit Do not secure pipe...

Страница 4: ...ny spillage is contained or routed to avoid electrics or areas sensitive to water damage As part of the AB airgap CAT 5 fluid isolation the APU has a weir type overflow on the right hand side water wi...

Страница 5: ...nit on either the left or right The pumps are connected to the tank via a rubber connector A pressure transducer monitors system pressure and if a reduction in system pressure is detected the controll...

Страница 6: ...which the APU Midi is located is flat and level 3 If possible locate the unit against a wall for added stability 4 If the APU Midi is located in an area that might be subjected to flooding mount the A...

Страница 7: ...dance with the current national electrical regulations and installed by a qualified person 5 12 Safety In the interests of electrical safety a 30 mA residual current device R C D not supplied should b...

Страница 8: ...for boiler chiller shut down in the event that the APU Midi detects system pressure above the Hi alarm pressure or below the Lo alarm pressure The boiler interlock contact will be open circuit below t...

Страница 9: ...to function correctly the following conditions must be met If these conditions have not been met the commissioning process should not continue z Ensure the system connection has been made into the hea...

Страница 10: ...ctivity Pump run time Alarm reset 6 18 Setting menu Pass code protected if set The following functions can be set and modified System pressure 2 see Fig 20 Sets the required system pressure Set in 0 1...

Страница 11: ...able from 3 to 120 seconds pre set to 3 seconds Increasing this time will reduce un wanted APU Midi operation during rapid system pressure fluctuations circulator pump starts Pump test Forces pump 1 L...

Страница 12: ...pressure error and the red error light will illuminate on the front of the APU this is normal z Open the isolation valve on the outlet of the APU and the APU will run and start to fill the system 6 2...

Страница 13: ...on the screen may be shown slightly higher than the set pressure whilst the pump is running As soon as the pump stops this displayed reading will settle back to the actual system pressure During the n...

Страница 14: ...ng order after a prolonged period of maintainance the following steps should be taken 1 Inspect the APU for signs of damage 2 Check APU tank for debris remove debris and clean tank if needed Debris ma...

Страница 15: ...em Activate system fill option to suppress alarm for 24 hours Leak in system Check system for leakage Monitor using system fill volume log reset if needed Increase pump run time limit Activity high al...

Страница 16: ...pump operation Float valve operation x Level probe operation x Water condition x Exp vessel pre charge x Comments Service No 2 Date Engineer name Company name Tel No System pressure bar Differential...

Страница 17: ...Office Gloucester Road Cheltenham GL51 8NR United Kingdom Object of the declaration Pressurisation Unit The object of the declaration described above is in conformity with the relevant Union harmonisa...

Страница 18: ...34...

Страница 19: ...com www adey com Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey com trademarks for a list of ADEY marks Copyrigh...

Отзывы: