Controller overview

 

The pressurisation unit controller is designed to be intuitive to use and allows  

 

 

functions and alarms to be set by the installer/user . It also allows faults to be  

 

 

monitored and logged to enable easier system fault diagnosis .

 

The functions are set using the 4 buttons (A, B, C & D) on the front of the    

 

 

controller and with the help of on screen prompts via the back lit LCD display .  

 

 

On the front of the APU a green ‘power on’ light will be displayed whilst the  

 

 

unit is powered . If an alarm or error is raised the red ‘Error’ light will be  

 

 

 displayed . 

 

A number of pressure set points can be set using the menus, these set points are    

 

detailed below, 1 to 4 and in the description of the function .

 

Button A Scrolls up through menus or increases set values .

 

Button B Enters menus or selects values .

 

Button C Scrolls down through menus or reduces set values .

 

Button D Returns to previous menu

6 .16 

Function list & explanation

 

The functions are contained within an initial display and 3 menus:-

 

Setting menu (pass code protected) see Section 6 .18 .

 

Advanced setting menu (pass code protected) see Section 6 .19 .

 

Test menu (pass code protected) see Section 6 .20 .

6 .17 

Initial display

 

On start up, and during operation, if the APU has had no button inputs for    

 

 

1 minute, a home screen (see Section 7 .11) will be displayed with system    

 

 

pressure, tank water level, any active alarm and any pump that is operating at  

 

 

the time . By using buttons A & C to scroll up or down the following screens will be    

 displayed:-

 

System pressure

 

Active errors

 

System fill status

 

Pump activity

 

Pump run time

 

Alarm reset 

6 .18 

Setting menu

 

(Pass code protected, if set)

 

The following functions can be set and modified:-

System pressure (2) 

see Fig . 20

Sets the required system pressure.

 Set in 0 .1 bar increments up 

to the maximum set value for the pressurisation unit model - Midi 130 

& 230 - 3 .5 bar max; Midi 150 & 250 - 4 .1 bar max .

Differential pressure (3)

see Fig . 20

Sets the pressure at which the pressurisation unit will turn 

on at as the system pressure falls.  Relative to the system 

pressure.

 Set in 0 .05 bar increments below the System pressure (2), 

cannot be set above 0 .1 bar below the System pressure (2) .

Hi Alarm (1)

see Fig . 20

Sets high system pressure alarm.

 Set in 0 .05 bar increments 

above the System pressure (2) . Cannot be set below System pressure 

+ 00 .5 bar . Alarm auto resets when system pressure is reduced below 

alarm level .

Lo Alarm (4)

see Fig . 20

Sets low system pressure alarm.

 Set in 0 .05 bar increments 

below the System pressure (2) - Differential pressure (3) - 0 .05 bar . 

Alarm auto resets when system pressure is increased above alarm 

level

System fill

Turns on system fill option

 .  System fill option will turn off once 

the System pressure (2) has been reached or a period of 24 hours has 

passed since it was set to ‘on’ . Lo alarm and Max runtime functions 

are disabled whilst System fill is turned on . Pumps will stop if the 

System pressure (2) or Hi alarm pressure (1) is reached .

Start Activity High

Alarm triggered if the APU starts more than the preset 

limit in 24 Hours.

Set to minimum of 100 starts per 24 hrs . Set in increments of 100 .

TIME

PR

ESSU

R

E

HIGH ALARM SET VALUE (1)

LOW ALARM SET VALUE (4)

SYSTEM PRESSURE SET VALUE (2)
DIFFERENTIAL SET VALUE (3)

PUMP 'OFF'

PUMP 'ON'

SYSTEM FILL MODE

NORMAL OPERATION

SY

ST

EM

PR

ES

SU

RE

Fig. 20

Fig. 21

A

B

C

D

Содержание CP1-03-04913

Страница 1: ...Installation and servicing Midi 135 150 235 250 Digital Pressurisation Unit...

Страница 2: ...rated with the front cover in place z In the interests of electrical safety a 30 mA residual current device R C D not supplied should be installed in the supply circuit This may be part of a consumer...

Страница 3: ...l cause leakage 1 16 Secure pipework Ensure pipework to and from pump is independently supported clipped to prevent forces being transferred to inlet and outlet branches of the unit Do not secure pipe...

Страница 4: ...ny spillage is contained or routed to avoid electrics or areas sensitive to water damage As part of the AB airgap CAT 5 fluid isolation the APU has a weir type overflow on the right hand side water wi...

Страница 5: ...nit on either the left or right The pumps are connected to the tank via a rubber connector A pressure transducer monitors system pressure and if a reduction in system pressure is detected the controll...

Страница 6: ...which the APU Midi is located is flat and level 3 If possible locate the unit against a wall for added stability 4 If the APU Midi is located in an area that might be subjected to flooding mount the A...

Страница 7: ...dance with the current national electrical regulations and installed by a qualified person 5 12 Safety In the interests of electrical safety a 30 mA residual current device R C D not supplied should b...

Страница 8: ...for boiler chiller shut down in the event that the APU Midi detects system pressure above the Hi alarm pressure or below the Lo alarm pressure The boiler interlock contact will be open circuit below t...

Страница 9: ...to function correctly the following conditions must be met If these conditions have not been met the commissioning process should not continue z Ensure the system connection has been made into the hea...

Страница 10: ...ctivity Pump run time Alarm reset 6 18 Setting menu Pass code protected if set The following functions can be set and modified System pressure 2 see Fig 20 Sets the required system pressure Set in 0 1...

Страница 11: ...able from 3 to 120 seconds pre set to 3 seconds Increasing this time will reduce un wanted APU Midi operation during rapid system pressure fluctuations circulator pump starts Pump test Forces pump 1 L...

Страница 12: ...pressure error and the red error light will illuminate on the front of the APU this is normal z Open the isolation valve on the outlet of the APU and the APU will run and start to fill the system 6 2...

Страница 13: ...on the screen may be shown slightly higher than the set pressure whilst the pump is running As soon as the pump stops this displayed reading will settle back to the actual system pressure During the n...

Страница 14: ...ng order after a prolonged period of maintainance the following steps should be taken 1 Inspect the APU for signs of damage 2 Check APU tank for debris remove debris and clean tank if needed Debris ma...

Страница 15: ...em Activate system fill option to suppress alarm for 24 hours Leak in system Check system for leakage Monitor using system fill volume log reset if needed Increase pump run time limit Activity high al...

Страница 16: ...pump operation Float valve operation x Level probe operation x Water condition x Exp vessel pre charge x Comments Service No 2 Date Engineer name Company name Tel No System pressure bar Differential...

Страница 17: ...Office Gloucester Road Cheltenham GL51 8NR United Kingdom Object of the declaration Pressurisation Unit The object of the declaration described above is in conformity with the relevant Union harmonisa...

Страница 18: ...34...

Страница 19: ...com www adey com Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey com trademarks for a list of ADEY marks Copyrigh...

Отзывы: