EN
sigfox MODBUS MASTER - Guide utilisateur / User guide version V1.0.1
67
Page
of 80
FR
4.2.1 Product configuration request frame
This frame (0x01) allows to inform the product via the network that it must resend the product configuration uplink frame (0x10).
0
1
2
3
4
5
6
7
Code
PAYLOAD
0x01
X
X
X
X
X
X
X
4.2.2 Network configuration request frame
This frame (0x02) allows to inform the product via the network that it must resend the network configuration uplink frame (0x20).
0
1
2
3
4
5
6
7
Code
PAYLOAD
0x02
X
X
X
X
X
X
X
4.2.3 Specific register VALUE request frame
This frame (0x41) allows to change the VALUE of requested registers.
0
1
2
3
4
5
…
7
Code
PAYLOAD
0x40
CONF ID1
CONF ID2
CONF ID3
X
X
X
CONF IDn
Description of the frame:
• Bytes 1 to N : CONF IDX (8bits): index of the register to be sent. The corresponding register is 300 + CONF IDX VALUE .
For example, if CONF ID1 =0x14 (so 20 in decimal), the product will send back the value of register number 320.
The associated uplink frame has the code 0x31 (see paragraph 4.1.5).
0
1
2
3
4
5
…
11
Code
PAYLOAD
0x31
Status
VALUE 1
VALUE 1
VALUE 2
VALUE 3
VALUE 3
X
In this example: CONF ID1 is a 2-byte register, CONF ID2 a 1-byte register and CONF ID3 a 2-byte register.
If an error is detected in the request, the returned 0x31 frame will be empty.
IMPORTANT : The user can specify several CONF IDs in his downlink frame but it is his responsibility to verify that according to the protocol the
size of the data available in a downlink frame will be large enough to contain all the desired data. Otherwise, the application will only send the
first VALUEs.