2.4. Configuring the SIGFOX PULSE
Your SIGFOX PULSE is configured via the combination of switches. The following settings can be changed:
• The meter type
• The pulse width
• The transmission frequency
Note:
configuration via switches lets you use 2 meters of the same type (2 water, 2 gas, …).
CONFIGURATION TABLE:
Parameter
Value
SW1
SW2
SW3
SW4
SW5
SW6
Meter type
Electricity
ON
OFF
Water
OFF
OFF
Gas
OFF
ON
Heat
ON
ON
Pulse width
1L / 10dm
3
/ 1Wh
OFF
OFF
10L / 10dm
3
/ 10Wh
OFF
ON
100L / 100dm
3
/ 100Wh
ON
OFF
1000L / 1m
3
/ 1000Wh
ON
ON
Transmission frequency
2 frames per day
OFF
OFF
50 frames per day
OFF
ON
100 frames per day
ON
OFF
140 frames per day
ON
ON
PLEASE NOTE
: You must set your switches before activating the meters. Once the fraud wire for each of the meters has been installed and the
SigFox PULSE has been started via magnet, the configuration with the switchs can no longer be possible.
If the configuration has any difference between the switchs and the product register value, the consistency error bit will be set to on in the
frame. This consistency verification is carried out every minute.