Once configuration of the product has been completed and its installation finalized, the product is ready to be started.
The product is started using a magnet placed on the upper part of the product (cf diagram below). The magnet must be kept in position for a
minimum of 6 seconds in order to confirm start-up of the product.
Once the AMR PULSE validates its start-up, it immediately transmits a data frame and history frames.
The AMR PULSE does not have an external LED showing its status. To make sure the product has started properly, we advise placing a data
receiver close to your product before start-up with the magnet. You can then receive the start-up frames and confirm that your product is opera-
ting properly.
IMPORTANT NOTE 1
: once the AMR PULSE has started, it can no longer be switched off.
IMPORTANT NOTE 2
: if the magnet is placed on it a second time, the AMR PULSE switches to CONFIGURATION mode. A 4 minute period
starts in which the product can no longer transmit. After these 4 minutes have passed, the product switches back to OPERATING mode.
Installation and use
3.6. Starting the product with a magnet
Compression gland nut
Position of the magnet for
product start-up