4-7
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*86
Cancel Verify Keypad Display
0 = no
1 = yes
When enabled (1 = yes), this feature causes a “
CANCELED
ALARM”
display on the LCD keypad under the following conditions:
After the kissoff of the cancel message to the Central Station,
indicating a successful transmission.
When an alarm is successfully canceled before the Central Station
received the Alarm message. E.g., if an alarm is falsely triggered
and the user presses code + OFF before the dial delay time has
expired, the message will never go out to the CS.
When the Cancel report is not enabled and the system is disarmed:
a.
before
dialer delay expires (alarm report not sent) message
“Canceled Alarm” is displayed.
b.
after
dialer delay expires message “Canceled Alarm” is not
displayed.
*87
Misc. Fault Delay Time
0 = 15 secs
6 = 2-1/2 min #+12 = 8 min
1 = 30 secs
7 = 3 min
#+13 = 10 min
2 = 45 secs
8 = 4 min
#+14 = 12 min
3 = 60 secs
9 = 5 min
#+15 = 15 min
4 = 90 secs
#+10 = 6 min
5 = 2 min
#+11 = 7 min
Used with zones assigned to a configurable zone type with fault delay
on (selected in alarm/trouble processing prompt), and sets a zone
response time of 15 seconds to 15 min. It can be assigned to zones
with sensors that provide a trouble indication when an oil or gas tank
is low, or similar applications for critical condition monitoring where
a non-alarm response is desired and where the zone response time
should be very long to avoid reacting to normal transient faults.
*88
Exit Options
0 = all intrusion zones must be intact before
arming
1 = All intrusion zones except in exit path
(zone list 12) must be intact before
arming. Will go into alarm if not restored
at end of exit time
2 = All intrusion zones except in exit path
(zone list 12) must be intact before
arming. Will be bypassed if not restored
at end of exit time
3 = Final contact set: All intrusion zones
except in exit path (zone list 12) must
be intact before arming. Once armed,
exit delay remains on indefinitely until
the last zone, as defined in zone list 8,
is restored; then there is 5-second exit
delay before arming state is active
Select the desired option.
NOTE:
Must be “0” if system uses zone type 82 - blockschloss.
*89
Event Log Full Report Code
0 = disable; 1-F = see description above
59
If an Event Logging selection is made in field
90, a message can be
sent to the central station receiver when the log is 80% full. If the log
becomes full, new messages overwrite the oldest messages in the log.
*90
Event Log Enables
0 = no event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of
entries)
This system has the ability to record up to 250 events in a history log.
At any time, the downloader operator can then upload the log and
view or print out all or selected categories of the log. The downloader
operator can also clear the log. Event log can also be viewed at an
alpha keypad (see User Guide for log display format).
The display/printout at the central station will show the date, time,
event, and description of the occurrences.
Data Entry Example: To select Alarm/Alarm Restore” and
“Open/Close”, enter 9 (1+ 8); to select all events, enter #15.
*91
Option Selection
0 = none
4 = using Audio Alarm Verification (AAV) unit
8 = Enable Exit delay restart/reset ††
Multiple choice example: for both AAV and
Exit delay restart, enter # + 12 (4 + 8).
Select the desired options by adding the values of each desired option.
††“Exit Delay Restart/reset” option allows use of the [
] key to restart
the exit delay at any time when the system is armed STAY or
INSTANT. This feature also enables automatic exit delay reset,
which resets exit delay if the entry/exit door is re-opened and closed
before exit delay time expires after arming AWAY or MAXIMUM.
IMPORTANT:
AAV should not be used when Paging or Alarm
Reports are sent to a secondary number unless the monitoring zone
option is used (which pauses calls). Otherwise, the call to the
secondary number by the communicator after the alarm report will
prevent the AAV from taking control of the telephone line, and the
AAV “Listen in” session cannot take place.
Содержание VISTA-48D
Страница 1: ...VISTA 48D Security System Installation and Set Up Guide K0749 4EN 1 03...
Страница 2: ...ii...
Страница 28: ...Installation Instructions 3 8...
Страница 60: ...Installation Instructions 5 20...
Страница 75: ...8 5 NOTES...
Страница 76: ...Installation Instructions 8 6 NOTES...
Страница 79: ...9 3 Figure 17 Summary of Connections...