INSTALLATION INSTRUCTIONS
For use with QED control panels ONLY!
N7491V3 5/98
No. 5819
SHOCK PROCESSOR
TRANSMITTER
A
+
–
BA
TTER
Y
REED
SWITCH
(LOOP 2)
COVER PRY-0FF POINT
ALIGN MAGNET
WITH MARKS ON
CASE AND GUIDE
ON MTG. PLATE
MAGNET
(OBTAIN
SEPARATELY)
LOOP 1 TERMINALS
(See Detail “B”)
LOCKING TAB
RELEASE WINDOW
COVER
HOLDING
HOOKS (2)
COVER
TAMPER
SWITCH
HOLES “A” (2)
(SEE TEXT)
ANTENNA
DIP SWITCHES
See Detail “A”
DIP
SWITCHES
JUMPER PINS
See Detail “B”
SLOT FOR
CONCEALED
WIRING ACCESS
A
MAGNET
Diagram 2: No. 5819 (SHOWN WITH COVER REMOVED)
1
/
2
”
MAX
1
2
3
4
5
ON
TB2
TB1
MAGNETIC
ALIGNMENT
GUIDE
STRIP
RELEASE
FOR
BRACKET
CASE
HOLDING
POSTS
(2)
SLOT
FOR
WIRE
SCREW
HOLES
Diagram 1: MOUNTING PLATE
TABLE 1
SWITCH
RESPONSE TIME
SW1 (Most Sensitive)
1ms
SW2
2ms
SW3
5ms
SW4
10ms
SW5 (Least Sensitive)
20ms
JUMPER
PINS
SHOCK SENSOR
TERMINALS
(INPUT LOOP 1)
TABLE 2
JUMPER
COUNT
J1 (Most Sensitive)
1
J2
2
J3
4
J4
6
J5 (Least Sensitive)
8
J5 J4 J3 J2 J1
DETAIL B
DETAIL A
CONTACT
TERMINALS
(INPUT LOOP 3)
LOOP 3 TERMINALS
(See Detail “B”)
GENERAL INFORMATION
The No. 5819 Shock Processor Transmitter connects to
inertia type shock detectors which are mounted externally
to the transmitter case (detector not supplied) and is
intended for use only with a wireless alarm system that
supports QED 5800 Series wireless receivers.
The No. 5819 has three unique zones. The first is for a
wired, normally closed shock sensor loop (TB1), the
second is for a closed contact loop using the unit's built-in
magnetic reed switch in conjunction with a magnet, and
the third is for a wired closed circuit contact loop (TB2).
For U.L. installations, a contact may not be more than 3
feet from the transmitter.
The No. 5819 has a built-in cover tamper switch which
activates when the cover is removed.
INSTALLATION
Mounting
For proper orientation of the unit in relation to the
mounting plate, loop wiring, DIP switch adjustment, jumper
positions and/or magnet, read all of this section before
installing the unit.
The description that follows assumes that the unit will be
mounted as shown in the diagrams, with the magnet (if
used) located to the left of the unit. The unit can be
installed in any direction, as long as the relationship of the
unit to its mounting plate and (if used) magnet is
maintained.
Although two holes are provided in the unit that would
permit mounting directly to a surface (holes 'A" in Diagram
2), it is recommended that the mounting plate be used as
described below, for ease in removing the unit for
servicing should it become necessary.
Before mounting the transmitter permanently, conduct
Go/No Go tests (see QED control's instructions) to verify
adequate signal strength and reorient or relocate the
transmitter if necessary.
1.
Remove transmitter's cover by inserting the flat blade
of a small screwdriver into the pry-off slot nearest to
the cover's decorative ribs, and twisting the blade.
2.
Disengage the supplied mounting plate from the unit
by inserting the blade of a small screwdriver into the
locking tab release window (see Diagram 2) and
pressing it against the locking tab (see Diagram 1)
while sliding the plate downward along the case back.
3.
If a shock processor or wired contact loop is to be
used with concealed wiring, feed the wires through
the concealed wiring entry hole at one corner of the
plate . For surface wiring entry, a thin "breakout" area
is provided in the case wall.
4.
Install the mounting plate, with its case holding posts
pointing up (in this example), in the location selected.
5.
Attach the case back to the mounting plate by sliding
the keyhole slots in the case back down onto the
mounting plate's case holding posts. The locking tab
will click as the case back locks in place.
6.
If the unit's REED SWITCH is to be used, mount a
No. 5799 Magnet (obtained separately) adjacent to
the alignment marks on the case and the mounting
plate's alignment strip (see Diagram 2).
7.
Set response time using the DIP switches (use the tip
of a pen/pencil). SW1 sets a response time of 1ms
(milliSec.), SW5 sets a response time of 20ms. For a
response time of 0.5ms, set all DIP switches to OFF
(see Table 1).
8.
Set the pulse count jumper (see Table 2). The pulse
count is reset 3 seconds after the first pulse detected.
There is an LED on the PCB which flashes rapidly on
transmission.
NOTE: Make the device highly sensitive for the
purpose of enrolling the shock sensor loop (TB1)
into the system (turn SW. 1 on and put jumper on
J1). After the device has been enrolled, adjust
settings as described in steps 7 and 8 (above).