background image

fi

To replace batteries:
1.

Remove the detector from its mounting plate by twisting the detector counter-
clockwise. Remove batteries, if replacing, and dispose  properly.

2.

Install two new 3-volt CR123A Lithium batteries in the battery compart-
ment.  Follow the polarity diagram inside the compartment.

3.

Reinstall the smoke detector onto the mounting plate by turning the
detector clockwise.

4. Test the detector as described in the TESTING TRANSMITTER SIG-

NAL section of this manual. The LED should flash about once every 40
seconds to indicate normal operation. If the batteries are not installed
correctly, the smoke detector will not operate and the batteries may be
damaged. If the detector does not appear to be sending a signal during
any of the tests, check for correct battery installation.

Test Module
      Port

Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service

Test Switch

Figure 1.  5808 Wireless Smoke/ Heat Detector

PROGRAMMING
The smoke detector’s ID must be enrolled in the QED control panel during
installation of the system. The QED control panel should be programmed
to enroll the  5808 as an “RF” unit (must be programmed as “supervised RF”
for UL installations).  Put the QED control panel in the program
ming mode and perform the following:
With the QED control panel, program the detector as loop 1 and either
manually enter the serial number that is on the label of the  5808, or press
the test switch to cause a transmission.  Additional transmissions will cause
the “Confirm” display to appear on the keypad display.

See the QED control unit’s installation instructions for further details.

Before installing detectors, please thoroughly read these installation instruc-
tions and Manual I56-407, 

Guide for Proper Use of System Smoke Detectors,

which provides detailed information on detector spacing, placement, zoning,
wiring, and special applications. Copies of this manual are available from
ADEMCO.

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
WARNING: Do not use the maintenance signal as an indication that the
detector has reached the limits of its nominal sensitivity range. Maintenance
only indicates that the detector may need cleaning or can no longer respond
to smoke and shall not be used as a sensitivity indicating means.

GENERAL DESCRIPTION
The 5808 photoelectronic smoke/heat detector with built-in wireless transmit-
ter is intended for use with wireless alarm systems that support QED 5800
series devices. Refer to QED control communicator installation instructions
for compatibility. The  5808 smoke/heat detector can be used with 5881 series
(L, M, H) and 5881EH receivers for residential installations. The  5808 smoke/
heat detector can be used with the 5881EH receiver for commercial installa-
tions. The transmitter can send alarm, tamper, maintenance (when QED
control panels are equipped to process maintenance signals), and battery
condition messages to the QED system's receiver.  The maintenance signal
will either indicate that the photo chamber requires cleaning or that the detector
can no longer respond to smoke and may need replacement. Refer to the
wireless system's instructions for the maximum number of transmitters that can
be supported.

The  5808 sounds its built-in horn when smoke reaches the detector (the
LED also flashes rapidly) or when the air temperature reaches 135° F (the
LED flashes normally, about once every 40 seconds). A message is also
sent to the wireless QED control panel and the smoke detector's ID number
is displayed at the console. The alarm message is transmitted every 4
seconds until the smoke condition has cleared and the detector has reset.
About 1 second after the horn stops, a RESTORE message is transmitted
to the QED control panel and the ID number can be cleared from the panel.
During normal, maintenance, and low battery conditions, the LED flashes
approximately once every 40 seconds.

BATTERY INSTALLATION AND REPLACEMENT
The 5808 is powered by two 3-volt CR123A or DL123A Lithium batteries
(included). The detector checks for low batteries at every normal LED flash.
If a low battery is detected, the transmitter sends a low battery message to
the QED control panel, which beeps and displays the detector's ID. This
condition will exist for a minimum of seven days, and then the detector's
horn will "chirp" about every 40 seconds. The batteries should be replaced
BEFORE the chirps begin. BE SURE TO REPLACE BOTH BATTERIES
WITH FRESH ONES.

AD300-00-00

I56-918-06

ADEMCO, 165 Eileen Way, Syosset, New York 11791

AD300-00-00

4

I56-918-06

© ADEMCO 1998

WARNING

LIMITATIONS OF SMOKE DETECTORS/TRANSMITTERS

This smoke detector is designed to activate and initiate

activate and initiate

activate and initiate

activate and initiate

activate and initiate emergency

action, but will do so only when used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72.....

Smoke detectors will not work without power.

Smoke detectors will not work without power.

Smoke detectors will not work without power.

Smoke detectors will not work without power.

Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off for any reason.

Alarm signal sent by the wireless transmitter in this detector may be
blocked or reflected by metal before reaching the alarm receiver. Even
if the signal path has been recently checked, blockage can occur if a
metal object is moved into the path.

Smoke detectors will not sense fires which start where smoke does

Smoke detectors will not sense fires which start where smoke does

Smoke detectors will not sense fires which start where smoke does

Smoke detectors will not sense fires which start where smoke does

Smoke detectors will not sense fires which start where smoke does
not reach the detectors.

not reach the detectors.

not reach the detectors.

not reach the detectors.

not reach the detectors. Smoldering fires typically do not generate a lot
of heat which is needed to drive smoke up to the ceiling where the smoke
detector is usually located. For this reason, there may be large delays in
detecting a smoldering fire with either an ionization-type detector or a
photoelectric-type detector. Either one of them may alarm only after
flaming has initiated, which will generate the heat needed to drive the
smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs, or on the other side of
a closed door may not reach the smoke detector and alarm it. A detector
cannot quickly detect, or sense at all, a fire developing on another level
of a building. Alarm warning devices, such as bell or horns, may not alert
people or wake up sleepers if they are located on the other side of closed
or partly open doors, or on another level. Persons may not hear a
warning device over the noise levels of a radio, air conditioner or other
appliances, or traffic. For this reason, detectors shall be located on

detectors shall be located on

detectors shall be located on

detectors shall be located on

detectors shall be located on

every level and in every bedroom within a building. 

every level and in every bedroom within a building. 

every level and in every bedroom within a building. 

every level and in every bedroom within a building. 

every level and in every bedroom within a building. Alarm warning
devices, however loud, may not warn hearing-impaired people or waken
deep sleepers.

Smoke detectors shall be located in any room where an alarm

Smoke detectors shall be located in any room where an alarm

Smoke detectors shall be located in any room where an alarm

Smoke detectors shall be located in any room where an alarm

Smoke detectors shall be located in any room where an alarm
control is located, or in any room where alarm control connections

control is located, or in any room where alarm control connections

control is located, or in any room where alarm control connections

control is located, or in any room where alarm control connections

control is located, or in any room where alarm control connections
to an AC source or phone lines are made. 

to an AC source or phone lines are made. 

to an AC source or phone lines are made. 

to an AC source or phone lines are made. 

to an AC source or phone lines are made. If detectors are not so
located, a fire within any of these rooms could prevent the QED control
from reporting a fire.

Smoke detectors have sensing limitations, too.

Smoke detectors have sensing limitations, too.

Smoke detectors have sensing limitations, too.

Smoke detectors have sensing limitations, too.

Smoke detectors have sensing limitations, too. Ionization detectors
and photoelectronic detectors are required to pass fire tests of the
flaming and smoldering types. This is to ensure that both can detect a
wide range of fires. Ionization detectors offer a broad range of fire-
sensing capability, but they are somewhat better at detecting fast-
flaming fires than slow-smoldering fires. Photoelectronic detectors sense
smoldering fires better than flaming fires, which have little, if any, visible
smoke. Because fires develop in different ways, and are often unpredict-
able in their growth, neither type of detector is always best, and a given
detector may not always provide early warning of a specific type of fire.

A78-2332-01

5808 Photoelectronic Smoke/Heat Detector with

5808 Photoelectronic Smoke/Heat Detector with

5808 Photoelectronic Smoke/Heat Detector with

5808 Photoelectronic Smoke/Heat Detector with

5808 Photoelectronic Smoke/Heat Detector with

Built-in 

Built-in 

Built-in 

Built-in 

Built-in Wireless 

Wireless 

Wireless 

Wireless 

Wireless T

T

T

T

Transmitter Installation Instructions

ransmitter Installation Instructions

ransmitter Installation Instructions

ransmitter Installation Instructions

ransmitter Installation Instructions

SPECIFICATIONS

SPECIFICATIONS

SPECIFICATIONS

SPECIFICATIONS

SPECIFICATIONS
Power  Source:

Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo
CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)

Maintenance Limits (Maintenance signal
is activated at either smoke level):

Hot Sensitivity: 0.65% ± 0.15% per foot
Cold Sensitivity: less than 6% per foot

Height:

2.5 inches (14 cm)

Diameter:

5.5 inches (64 mm)

Weight:

0.7 lb. (310 g)

Operating Ambient Temperature Range:

4.4° to 37.8° C (40° to 100° F)

Operating Humidity Range:

5% to 95% Relative Humidity

Heat Sensor:

135° F Fixed Temperature Electronic Thermistors

Agency Listings:

UL 217;  UL 268 – Residential, Commercial Installations

ADEMCO ONE-YEAR LIMITED WARRANTY

ADEMCO ONE-YEAR LIMITED WARRANTY

ADEMCO ONE-YEAR LIMITED WARRANTY

ADEMCO ONE-YEAR LIMITED WARRANTY

ADEMCO ONE-YEAR LIMITED WARRANTY

Alarm Device Manufacturing Company, a Division of Pittway Corporation
(“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security
equipment (the “product”) to be free from defects in materials and
workmanship for one year from date of original purchase, under normal
use and service. Seller’s obligation is limited to repairing or replacing, at
its option, free of charge for parts, labor, or transportation, any part proven
to be defective in materials or workmanship under normal use and service.
Seller shall have no obligation under this warranty otherwise if the product
is altered or improperly repaired or serviced by anyone other than the
seller. In case of defect, contact the security professional who installed
and maintains your security system or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties,
obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES
WHICH EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WAR-
RANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN
CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED
WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICU-
LAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A
PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE.
ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT
NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY,
MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF ORIGINAL
PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE
FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR
BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSO-
EVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER’S
OWN NEGLIGENCE OR FAULT. Some states do not allow limitations on
how long an implied warranty lasts or the exclusion of incidental or
consequential damages, so above limitation or exclusion may not apply
to you.
Seller does not represent that the product may not be compromised or
circumvented; that the product will prevent any personal injury or property
loss by burglary, robbery, fire or otherwise; or that the product will in all
cases provide adequate warning or protection. Buyer understands that a
properly installed and maintained alarm my only reduce the risk of a
burglary, robbery, or fire occurring without providing an alarm, but it is not
insurance or a guarantee that such will not occur or that there will be no
personal injury or property loss as a result. CONSEQUENTLY, SELLER
SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP-
ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE
PRODUCT FAILED TO GIVE WARNING. However, if seller is held liable,
whether directly or indirectly, for any loss or damage arising under this
Limited Warranty or otherwise, regardless of cause or origin, Seller’s
maximum liability shall not in any case exceed the purchase price of the
product, and shall be the  complete and exclusive remedy against Seller.
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state. No increase or alteration, written or
verbal, to this warranty is authorized.

In general, detectors cannot be expected to provide warnings for fires
resulting from inadequate fire protection practices, violent explosions,
escaping gases that ignite, improper storage of flammable liquids like
cleaning solvents that ignite, other similar safety hazards, arson, smoking
in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to
dilution of smoke densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent detector maintenance.

To keep your equipment in excellent working order, ongoing mainte-
nance is required per the manufacturer’s recommendations and UL and
NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72, the National Fire Alarm Code, shall be followed. A preventative
maintenance agreement should be arranged through the local
manufacturer’s representative. Though smoke detectors are designed
for long life, they may fail at any time. Any smoke detector, fire alarm
equipment, or any component of that system which fails shall be repaired
or replaced as soon as possible.

NOTE:

Before removing the detector, notify the proper authorities
that the smoke detector system is undergoing maintenance
and will be out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms.

1. Remove the detector cover by placing a small-bladed screwdriver in

the cover removal slot and twisting it slightly until the cover can be
turned counterclockwise for removal.

2. Remove the screen by pulling it straight out (see Figure 8). Vacuum the

screen thoroughly.

3. Clean the black vaned chamber piece by vacuuming or blowing out

dust and particles.

4. To reinstall the screen, rotate the screen on the housing until it drops

into the alignment slots. Carefully push the screen onto the base,
making sure it fits tightly to the chamber. Replacement screens are
available (order part number RS23).

5. Replace the cover by rotating it clockwise until it locks in place.
6. Reinstall the detector into the system, enable system operation, and

notify the proper authorities that the system is back on line.

For use with QED control panel ONLY!

R

Previous Menu

Отзывы: