background image

5808 Series
Photoelectric
Smoke/Heat
Detector with
built-in wireless
transmitter

FEATURES

The 5808 and 5808C Commercial/Residential Photoelectric Smoke and Heat Detectors have a
built-in wireless transmitter and two concealed thermistors for heat detection. For difficult to
wire locations, room aesthetics or even hazardous materials, like asbsestos above a drop
ceiling, installation of these wireless devices provides the cost effective solution.

The 5808 and 5808C provide versatility for fire detection system designs and represents
ADEMCO’s ability to meet virtually any installation challenge using commercial wireless,
addressable or conventional detection devices.

The 5808/5808C photoelectronic smoke/heat detector with built-in wireless transmitter is
intended for use with wireless alarm systems. The 5808/5808C smoke/heat detector can be
used with 5881 series (L, M, H) for residential and 5881EH receivers for commercial
installations. The transmitter can send alarm, tamper, maintenance (see control panel
specifications) and battery condition messages to the system’s receiver. The maintenance
signal will either indicate that the photochamber requires cleaning or that the detector can no
longer respond to smoke and may need replacement. Refer to the wireless system’s
instructions for the maximum number of transmitters that can be supported.

The 5808 sounds its built-in horn when smoke reaches the detector (the LED also flashes
rapidly) or when the air temperature reaches 135°F (the LED flashes normally, about once
every 40 seconds). A message is also sent to the wireless control panel and the smoke
detector’s ID number is displayed at the console. The alarm message is transmitted every four
seconds until the smoke condition has cleared and the detector has reset. About one second
after the horn stops, a RESTORE message is transmitted to the control panel and the ID
number can be cleared from the panel. During normal, maintenance, and low battery
conditions, the LED flashes approximately once every 40 seconds. 

SPECIFICATIONS

The 5808C is identical to the 5808 exept that it has no sounder to conflict with building
notification appliances.

Power source:

Two-volt CR123A lithium batteries (included). 
Replace with Duracell DL123A, Sanyo CR123A,
Panasonic CR123A, ADEMCO 466, or Varta
CR123.

Maintenance limits (maintenance)
is activated at either smoke level):

Hot sensitivity: 0.65% + 0.15% per foot Cold
sensitivity: less than 6% per foot

Height:

2.5 inches (14 cm), 

Diameter:

5.5 inches (64 mm),

Weight:

0.7 lb. (310 g)

Operating ambient temperature range:

4.4° to 37.8°C (40° to 100°F)

Operating humidity range:

5% TO 95% relative humidity

Heat sensor:

135°F fixed temperature electronic thermistors

Agency listings:

UL 217; UL 268 - Residential, Commercial
Installations

5808/5808C

smoke/heat detector

An ADEMCO Group Company

The 5808 and 5808C

provide versatility for

fire detection system

designs and represents

ADEMCO’s ability to

meet virtually any

installation challenge

using commercial

wireless, addressable

or conventional

detection.

5808/5808C

Wireless Photoelectric Smoke Detector

Содержание 5808 Series

Страница 1: ...lashes rapidly or when the air temperature reaches 135 F the LED flashes normally about once every 40 seconds A message is also sent to the wireless control panel and the smoke detector s ID number is displayed at the console The alarm message is transmitted every four seconds until the smoke condition has cleared and the detector has reset About one second after the horn stops a RESTORE message i...

Страница 2: ...his detector has a built in tamper switch that will cause a CHECK signal to be displayed at the console of the detector if it is removed from its installation bracket The mounting bracket can also be made tamer proof by breaking off the smaller tab at the scribed line thus preventing removal of the detector without a tool To remove the detector use a small screwdriver to depress the tamer proof ta...

Страница 3: ...er should test the unit at least weekly 1 Activate the wireless system s TEST mode from the console 2 Depress and hold the smoke detector s TEST switch and the detector should immediately transmit and alarm signal to the control panel The built in horn will start to sound about 2 5 seconds after depressing the button 3 The wireless system s console should emit at least three audible sounds when th...

Страница 4: ...tate the screen on the housing until it drops into the alignment slots Carefully push the screen onto the base making sure it fits tightly to the chamber Replacement screens are available order part number RS23 5 Replace the cover by rotating it clockwise until it locks into place 6 Reinstall the detector into the system enable the system operation and notify the proper authorities that the system...

Отзывы: