Ordering Information

Part No.

Description

5808

Smoke/Heat
Detector
w/Sounder

5808C

Smoke/Heat
Detector

Maintenance

Note: Before removing the detector, notify the proper authorities that the smoke detector

system is undergoing maintenance and will be out of service. Disable the zone or system

undergoing maintenance to prevent unwanted alarms.

1.. Remove the detector cover by placing a small bladed screwdriver in the cover removal

slot and twisting it slightly until the cover can be turned counterclockwise for removal.

2.  Remove the screen by pulling it straight out. Vacuum the screen thoroughly.

3.  Clean the black vaned chamber piece by vacuuming or blowing out dust and particles.

4.  To reinstall the screen, rotate the screen on the housing until it drops into the alignment

slots. Carefully push the screen onto the base, making sure it fits tightly to the chamber.

Replacement screens are available (order part number RS23).

5.  Replace the cover by rotating it clockwise until it locks into place.

6.  Reinstall the detector into the system, enable the system operation, and notify the proper

authorities that the system is back on line.

To keep your equipment in excellent working order, ongoing maintenance is required per the

manufacturer’s recommendations and UL and NFPA standards. At a minimum, the

requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A

preventative maintenance agreement should be arranged through the local manufacturer’s

representative. Though smoke detectors are designed for long life, they may fail at any time.

Any smoke detector, fire alarm equipment, or any component of that system which fails

shall be repaired or replaced as soon as possible.

An ADEMCO Group Company

5808/5808C

smoke/heat detector

Содержание 5808 Series

Страница 1: ...lashes rapidly or when the air temperature reaches 135 F the LED flashes normally about once every 40 seconds A message is also sent to the wireless control panel and the smoke detector s ID number is displayed at the console The alarm message is transmitted every four seconds until the smoke condition has cleared and the detector has reset About one second after the horn stops a RESTORE message i...

Страница 2: ...his detector has a built in tamper switch that will cause a CHECK signal to be displayed at the console of the detector if it is removed from its installation bracket The mounting bracket can also be made tamer proof by breaking off the smaller tab at the scribed line thus preventing removal of the detector without a tool To remove the detector use a small screwdriver to depress the tamer proof ta...

Страница 3: ...er should test the unit at least weekly 1 Activate the wireless system s TEST mode from the console 2 Depress and hold the smoke detector s TEST switch and the detector should immediately transmit and alarm signal to the control panel The built in horn will start to sound about 2 5 seconds after depressing the button 3 The wireless system s console should emit at least three audible sounds when th...

Страница 4: ...tate the screen on the housing until it drops into the alignment slots Carefully push the screen onto the base making sure it fits tightly to the chamber Replacement screens are available order part number RS23 5 Replace the cover by rotating it clockwise until it locks into place 6 Reinstall the detector into the system enable the system operation and notify the proper authorities that the system...

Отзывы: