When installing the SR-20RM into a rack, the selected location should meet environmental standards as
described below.
Rack Space and Airflow Considerations
To allow for adequate airflow, technicians should observe the following space and airflow requirements when
deciding where to install a rack.
• Leave a minimum clearance of 12in (30.48cm) in front of the rack.
• Leave a minimum clearance of 8in (20.32cm) behind the rack
.
Temperature Considerations
Your SR-20RM is designed to operate at room temperature with its self-contained cooling.
Power Considerations
When properly configured and installed the SR-20RM can draw up to 800 Watts depending on the number,
load, and version of the BioDigitalPC
®
s used.
To prevent improper cooling of equipment, do not block the fans.
Section 2.1 - Preparing For Your SR-20RM
If using the dual feed redundant power solution (See Section 2.6.2), each power source must be
capable of supporting a maximum draw of 650 Watts.
Section 2 - SR-20RM Preparation