INSTALLATION AND MAINTENANCE INSTRUCTIONS 

FLOAT & THERMOSTATIC STEAM TRAPS 

FLT16 

 

GENERAL 

 

 

These  instructions  must  be  carefully  read  before  any  work  involving  products  supplied  by  VALSTEAM  ADCA 
ENGINEERING S.A. is undertaken. 
 

 

The installation procedure is a critical stage in a life of a float trap and care should be taken to avoid damage to 
the float trap or equipment. 

 

Warning! 

 

- At start up, the presence of small particles in the water (dirt, scale, weld splatters, etc) may cause an unperfected 
closure of the seat. If this occurs, proceed to an accurate cleaning. 
- Do not touch the equipment without appropriate protection during working operation because it may conduct heat 
if the used fluid is at high temperature.

 

- Before starting maintenance be sure that the equipment is not pressurized or hot. 
- The equipments must be used  within the  working temperature and pressure  limits laid down for them, otherwise 
they may fail (refer to nameplate and/or IS- Information Sheet). 
- Do not remove the nameplate attached to the equipment. Serial number and other useful information is stamped 
on it. 

 

INSTALLATION 

 

 

 

 
-  Before  to  install  remove  plastic  covers  placed  on  flanges  or  connection  ends.  The  equipment  has  an  arrow  or 
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction. 
- Install the steam trap in the point of the system, where the condensate tends to collect. 
It must be installed with the float lever in horizontal plane, so that it rises and falls vertically.

 

An ADCA strainer should be installed upstream of the trap. 

 

 

PMA: Max. allowable pressure

16 bar

FLT 16-4,5

4,5 bar

TMA: Max. allowable temperature

250 ºC

FLT 16-10

10 bar

PMO: Max. operating pressure

14 bar

FLT 16-14

14 bar

TMO: Max. operating temperature

198 ºC

LIMITING CONDITIONS

MAX. DIFFERENTIAL PRESSURE

 

 
Installation area requirements: 
 

 

The  installation  area  should  have  easy  access  and  provide  enough  space  for  maintenance  and  removing 
operations. 

 

 

The installation area should have the necessary firing system to prevent damage of the equipment due to over 
temperature/pressure cause by fire. 